-91-
■
The problem of missing the connector (INDOOR MAIN PCB ASSY)
Connectors
CN-POWER
(AC2)
CN-FAN
CN-DATA
CN-DISP1
CN-TH
CN-U/D
Condition
OPEN
OPEN
OPEN
OPEN
OPEN/SHORT
OPEN
• Malfunctions all indoor & outdoor unit.
• Malfunctions remocon, force, test operation mode.
• Malfunctions outdoor unit.
• Stop compressor and outdoor fan motor.
• The operation LED blinks 5 times.
• Communicaion error.
• Malfunctions remote contoller.
• Don't operate the power display module.
• The operation LED blinks once.
• Enable to receive remote singnal.
• Malfunctions UP/DOWN step motor.
• Don't operate louver.
• Malfunctions indoor fan motor.
Problem (error mode)
Summary of Contents for FMN0760NL
Page 94: ... 94 FMN1260NT FMN1860NT ...
Page 95: ... 95 FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Page 96: ... 96 FMN1860NV ...
Page 97: ... 97 2 Outdoor Unit MAIN P C B ASM FMU4480N6L ...
Page 98: ... 98 PCB PWB ASSY SUB ...
Page 99: ... 99 3 Display ASSY FMN1860NV FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Page 100: ... 100 4 SUB P W B ASSEMBLY FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Page 101: ... 101 Schematic Diagram 1 Indoor Unit FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Page 103: ... 103 FMN1260NFM B D ...
Page 104: ... 104 FMN1860NV RY 4WAY RY OUTFAN ...
Page 122: ...P No 3828A20208A August 2002 Printed in Korea ...