-84-
Turn on the main power.
When in air circulation mode, compressor/outdoor fan is stopped.
Turn off main power.
Check the electrical wiring diagram of Outdoor side.
Check the open or short of connecting wires between Indoor and Outdoor.
Check the sensor for Indoor temperature is attatched as close as to be effected by the
themperature of Heat Exchange (EVA.)
When the sensor circuit for Indoor temperature and connector are in bad connection or are
not engaged, Compressor/Outdoor fan is stopped.
• Check the related circuit of R02H(12.1K), R01H(1K), R04H(6.2K), R03H(1K), C01H(102),
C02H(102), Micom(pin No. 11, 12).
• Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).
Check the Relay(RY-PWR) for driving Compressor.
• Check the voltage between brown and blue cable of terminal to connect the Outdoor
(About AC220V / 240V).
• Check the related circuit of relay in Outdoor PCB Ass'y.
Operate Cooling Mode by setting the disired temperature of the remote controller is less
than one of the Indoor temperature by 1°C at least.
The Compressor/Outdoor Fan are unable to drive.
Trouble 3
Summary of Contents for FMN0760NL
Page 94: ... 94 FMN1260NT FMN1860NT ...
Page 95: ... 95 FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Page 96: ... 96 FMN1860NV ...
Page 97: ... 97 2 Outdoor Unit MAIN P C B ASM FMU4480N6L ...
Page 98: ... 98 PCB PWB ASSY SUB ...
Page 99: ... 99 3 Display ASSY FMN1860NV FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Page 100: ... 100 4 SUB P W B ASSEMBLY FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Page 101: ... 101 Schematic Diagram 1 Indoor Unit FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Page 103: ... 103 FMN1260NFM B D ...
Page 104: ... 104 FMN1860NV RY 4WAY RY OUTFAN ...
Page 122: ...P No 3828A20208A August 2002 Printed in Korea ...