Installation
21
Minimum clearance
1 600 mm
300 mm
915 mm
915 mm
300 mm
300 mm
300 mm
300 mm
600
mm
700
mm
700
mm
This product must be installed with clearance at the left, right, top, bottom and front of the product
as shown in the figure.
Make sure to keep at least a 300 mm distance between enclosure and enclosure, enclosure and other
devices.
Keep the 700 mm distance between the front door and in order to allow space for installation and
servicing.
If the door is closed, all other products should be away at least 300 mm from the front door for
safety operation.
Be sure not to place any object on top of the enclosure. Risk of fire or serious injury due to high
temperature.
If the ESS is installed outdoors with eaves, there must be at least 915 mm clearance to eaves.