Outdoor Unit
Electrical Wiring
■
Using Cool/Heat Selector Installation and Connection
• Connect wires as below figure at the hole of backside of Outdoor Unit Dry Contact.
• Insert the wire in the connection hole pushing the "Push" button.
• Setting Main PCB DIP SW of Master Outdoor Unit.
Cool/Heat Selector Installation and Connection(Heat pump only)
■
Without Cool/Heat Selector Installation and Connection
In case, try to set mode without Cool/Heat Selector and try to use other switch except from LG Outdoor
Cool/Heat Selector in field.
Connect signal terminal block as below figure and description.
- How to set mode without Cool/Heat Selector
• Cooling Mode Setting
➀ ➔
GND Connection
➁ ➔
Off (Open)
• Heating Mode Setting
➀ ➔
GND Connection
➁ ➔
GND Connection
• Fan Mode Setting
➀ ➔
Off (Open)
➁ ➔
GND Connection
Mode Change
Push Button
Heating
Outdoor Unit
GND
GND
GND
Fan
Cooling
SODU
IDU
INTERNET
DRY1
DRY2
GND
12V
GND
Mode Change
Push Button
Heating
Outdoor Unit
Fan
Cooling