26
Outdoor Unit
Refrigerant Piping
■
Combination of Y branch/header method
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header
Ⓕ
: Sealed piping
L 150m
40m
H 50mZ
Z
Z
Branch pipe can not be used after header
➲
Refrigerant pipe diameter from branch to branch (B,C)
➲
Total pipe length = A+B+C+a+b+c+d+e ≤ 300m
Longest pipe length
Equivalent pipe length(*)
A+B+b ≤ 150m
A+B+b ≤ 175m
Longest pipe length after 1st branch
B+b ≤ 40m
Difference in height(Outdoor Unit
↔
Indoor Unit)
H ≤ 50m (40m : Outdoor Unit is lower than Indoor Units)
Difference in height (Indoor Unit
↔
Indoor Unit)
h ≤ 15m
L
l
H
h
Downward Indoor Unit total capacity
[kW(Btu/h)]
≤ 5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8)
Ø15.88(5/8)
< 22.4(76,400)
Ø9.52(3/8)
Ø19.05(3/4)
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
WARNING
It is recommended that difference of piping length for pipes connected to the Indoor Unit is
minimized. Performance difference between Indoor Units may occur.
CAUTION
Indoor Unit should be installed at lower position than the header
* : Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose