24
Outdoor Unit
Refrigerant Piping
Allowable Length/Height Difference of Refrigerant Piping
■
Y Branch Method
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
L150m
H 50mZ
Z
l
40m
➲
Total pipe length = A+B+C+D+a+b+c+d+e ≤ 300m
Longest pipe length
Equivalent pipe length(*)
A+B+C+D+e ≤ 150m
A+B+C+D+e ≤ 175m
Longest pipe length after 1st branch
B+C+D+e ≤ 40m
Difference in height(Outdoor Unit
↔
Indoor Unit)
H ≤ 50m ( 40m : Outdoor Unit is lower than Indoor Units)
Difference in height (Indoor Unit
↔
Indoor Unit)
h ≤ 15m
L
l
H
h
CAUTION
Indoor Unit should be installed at lower position than the header
* : Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose