Installation Manual
25
■
Header Method
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Indoor Units
Ⓓ
: Sealed piping
L 150m
H 50mZ
Z
40m
WARNING
Pipe length after header branching (a~f)
It is recommended that difference in length of the pipes connected to the Indoor Units is
minimized. Performance difference between Indoor Units may occur.
Longest pipe length
Equivalent pipe length(*)
A+f ≤ 150m
A+f ≤ 175m
Longest pipe length after 1st branch
f ≤ 40m
Difference in height(Outdoor Unit
↔
Indoor Unit)
H ≤ 50m (40m : Outdoor Unit is lower)
Difference in height (Indoor Unit
↔
Indoor Unit)
h ≤ 15m
L
l
H
h
➲
Total pipe length = A+a+b+c+d+e+f ≤ 300m
CAUTION
Indoor Unit should be installed at lower position than the header
* : Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
Refrigerant Piping