Installation Manual
23
Selection of Refrigerant Piping
Selection of pipe size
Name
Size of main pipe
Pipe size of between branching sections
Connecting pipe size of indoor unit
Piping parts
No.
Outdoor unit
↓
1st branching section
Branching section
↓
Branching section
Branching section
↓
Indoor unit
Main pipe
①
②
③
Branching pipe
Indoor unit
connecting pipe
Outdoor unit capacity[kW(Btu/h)]
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
11.0(37,500)
Ø9.52(3/8)
Ø15.88(5/8)
14.5(49,500)
Ø9.52(3/8)
Ø15.88(5/8)
16.0(54,600)
Ø9.52(3/8)
Ø19.05(3/4)
Indoor unit capacity[kW(Btu/h)]
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
≤ 5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8)
Ø15.88(5/8)
Indoor unit capacity[kW(Btu/h)]
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
≤ 5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8)
Ø15.88(5/8)
< 22.4(76,400)
Ø9.52(3/8)
Ø19.05(3/4)
Outdoor unit
Gas pipe
Main pipe
Liquid pipe
Branching
pipe
Branching
pipe
Indoor unit
Refrigerant Piping