40 | HIGH STATIC
MUL
TI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
External Static Pressure Ranges
DUCTED HIGH STATIC
The table above shows the available E.S.P. range.
M2 Units, continued.
Model
Capacity
(MBh)
Mode
Setting Value
Standard
ESP (in wg)
CFM
Min. ESP (in wg) Max. ESP (in
wg)
ARNU283M2A4
28.0
High
(Factory Set)
High
101
0.24
845
0.16
0.71
Mid
95
676
Low
90
528
Standard
High
99
0.20
892
0.16
0.71
Mid
94
770
Low
89
645
ARNU363M2A4
36.0
High
(Factory Set)
High
109
0.24
1031
0.16
0.71
Mid
101
845
Low
95
676
Standard
High
105
0.20
1021
0.16
0.71
Mid
97
844
Low
92
695
ARNU423M2A4
42.0
High
(Factory Set)
High
120
0.24
1260
0.16
0.71
Mid
111
1076
Low
103
888
Standard
High
117
0.20
1262
0.16
0.71
Mid
108
1087
Low
103
917
Table 26: M2 Unit External Static Pressure Ranges.