External Static Pressure and Air Flow Tables
DUCTED HIGH STATIC
Table 19: BH Unit External Static Pressure and Air Flow Table.
BH, M2 Units
1. All static pressure air flow rates are listed in CFM.
2. The tables above show the correlation between air flow rates and external static pressure.
3. The tables above show the available external static pressure range.
If the external static pressure of the installed indoor unit is less than the lowest value (as mentioned in the table), the indoor unit components can fail.
Table 20: ARNU073~243M2A4 External Static Pressure and Air Flow Table.
Set Value
Static Pressure (in. wg)
0.12
0.15
0.19
0.23
0.27
0.31
0.35
0.39
0.47
70
95
-
-
-
-
-
-
-
-
80
187
-
-
-
-
-
-
-
-
90
275
215
127
102
-
-
-
-
-
100
360
286
212
134
117
-
-
-
-
110
445
410
311
258
208
148
-
-
-
120
554
501
420
357
297
230
177
155
-
130
632
583
547
466
417
339
268
215
152
140
724
671
622
569
540
459
427
364
205
145
756
703
682
618
569
509
480
392
279
150
795
752
703
667
622
565
505
491
364
BH Unit External Static Pressure and Air Flow Table.
M2 Unit External Static Pressure and Air Flow Table.
ARNU073~243M2A4 External Static Pressure and Air Flow Table.
Set value
Static Pressure (in wg)
0.16
0.24
0.31
0.39
0.47
0.55
0.63
0.71
Air Flow Rate [CFM]
65
70
75
530
80
672
267
85
879
486
173
90
974
720
276
95
1073
861
554
182
100
1168
1013
734
325
135
105
1267
1119
851
618
238
110
1363
1225
1077
784
406
195
115
1416
1334
1193
985
713
321
120
1380
1310
1108
868
632
263
125
1358
1236
1063
748
389
235
130
1310
1130
974
551
353
135
1298
1113
857
572
140
1431
1267
1052
792
145
1407
1233
980
150
1391
1207
155
1309