Heating Capacity Tables
ARNU283M2A4
Table 74: ARNU283M2A4 Heating Capacity Table.
DUCTED HIGH STATIC
Model No./
Capacity Index
Outdoor
Air Temp.
Indoor Air Temperature (°F DB)
59
61
64
67
70
73
76
80
°F DB °F WB TC
TC
TC
TC
TC
TC
TC
TC
ARNU283M2A4/
28.0
-21.6
-22.0
16.0
16.0
16.0
16.0
15.8
15.8
15.8
15.8
-17.1
-17.5
17.9
17.9
17.9
17.9
17.7
17.7
17.7
17.7
-12.6
-13
19.9
19.9
19.9
19.9
19.6
19.6
19.6
19.6
-7
-7.6
20.5
20.5
20.5
20.5
20.2
20.2
20.2
20.2
-4
-4.4
21.1
21.1
21.1
21.1
20.8
20.8
20.8
20.8
0
-0.4
21.7
21.7
21.7
21.7
21.7
21.4
21.4
21.4
5
4.5
24.6
24.3
23.9
23.9
23.9
23.9
23.9
23.9
10
9
25.5
25.5
25.5
25.2
25.2
25.2
25.2
25.2
15
14
27.1
27.1
27.1
27.1
27.1
27.1
26.8
26.5
20
19
28.7
28.7
28.7
28.7
28.0
28.0
27.6
27.3
25
23
29.9
29.9
29.9
29.9
29.9
29.3
29.0
27.6
30
28
30.6
30.6
30.6
30.6
30.6
29.9
29.0
27.6
35
32
31.5
31.5
31.5
31.5
31.2
30.6
29.0
27.6
40
36
32.8
32.8
32.8
32.8
31.5
30.6
29.0
27.6
45
41
34.0
34.0
34.0
33.1
31.5
30.6
29.0
27.6
47
43
35.3
35.0
34.7
33.1
31.5
30.6
29.0
27.6
50
46
37.8
36.2
34.7
33.1
31.5
30.6
29.0
27.6
55
51
38.6
36.5
34.7
33.1
31.5
30.6
29.0
27.6
60
56
38.6
36.5
34.7
33.1
31.5
30.6
29.0
27.6
TC: Total Capacity (MBh).
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Current certified ratings are available at
www.ahridirectory.org
.
For outdoor unit performance data, see the respective outdoor unit performance data
manuals on
https://lghvac.com/commercial
.
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.