TI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Electrical Data
Table 118: Vertical / Horizontal (NJ, NK Frames) Air Handler Unit Electrical Data.
VERTICAL / HORIZONTAL AIR HANDLER
Model
Voltage
Range
MCA MOP Rated Amps
(A)
Power Supply
Power Input
1
(W)
Hz
Volts
Phase
Max.
Cooling
Max.
Heating L / M / H at Factory Default
NJ Frames
ARNU123NJA4
208-230
1.4
15
1.12
60
208-230
1
228
228
47 / 64 / 80
ARNU183NJA4
1.4
1.12
228
228
64 / 80 / 90
ARNU243NJA4
1.4
1.12
228
228
64 / 96 / 120
ARNU303NJA4
1.4
1.12
228
228
94 / 133 / 180
ARNU363NJA4
1.4
1.12
228
228
133 / 180 / 230
NK Frames
ARNU423NKA4
208-230
2.25
15
1.8
60
208-230
1
366
366
186 / 215 / 260
ARNU483NKA4
2.25
1.8
366
366
186 / 264 / 330
ARNU543NKA4
2.25
1.8
366
366
264 / 312 / 370
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.
1
Max. power input is rated at maximum setting value.