12 | HIGH STATIC
MUL
TI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED HIGH STATIC
General Data
BH Units
Model No.
ARNU073BHA4 ARNU093BHA4 ARNU123BHA4 ARNU153BHA4 ARNU183BHA4 ARNU243BHA4
Cooling Mode Performance
Capacity (Btu/h)
7,500
9,600
12,300
15,400
19,100
24,200
Power Input
1
(W)
150
150
150
150
150
150
L/M/H Power Input at Factory Default (W)
49 / 52 / 58
52 / 58 / 67
58 / 67 / 78
58 / 78 / 90
78 / 90 / 103
103 / 117 / 132
Heating Mode Performance
Capacity (Btu/h)
8,500
10,900
13,600
17,100
21,500
27,300
Power Input
1
(W)
150
150
150
150
150
150
L/M/H Power Input at Factory Default (W)
49 / 52 / 58
52 / 58 / 67
58 / 67 / 78
58 / 78 / 90
78 / 90 / 103
103 / 117 / 132
Entering Mixed Air
Cooling Max. (°F WB)
76
76
76
76
76
76
Heating Min. (°F DB)
2
59
59
59
59
59
59
Unit Data
Refrigerant Type
3
R410A
R410A
R410A
R410A
R410A
R410A
Refrigerant Control
EEV
EEV
EEV
EEV
EEV
EEV
Sound Pressure
4
dB(A) (H/M/L)
34 / 33 / 32
35 / 34 / 33
37 / 35 / 34
39 / 37 / 34
40 / 38 / 37
42 / 41 / 40
Net Unit Weight (lbs.)
58.4
58.4
58.4
58.4
58.4
58.4
Shipping Weight (lbs.)
68.3
68.3
68.3
68.3
68.3
68.3
Communication Cable
5
(No. x AWG)
2 x 18
2 x 18
2 x 18
2 x 18
2 x 18
2 x 18
Fan
Type
Sirocco
Sirocco
Sirocco
Sirocco
Sirocco
Sirocco
Motor
1
1
1
1
1
1
Housing
2
2
2
2
2
2
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM)
Standard Mode
258 / 222 / 198
258 / 222 / 198
307 / 258 / 198
388 / 357 / 307 466 / 413 / 258
618 / 519 / 445
Airflow Rate H/M/L (CFM)
High Mode (Factory Set)
230 / 205 / 191
286 / 230 / 205
339 / 286 / 230
399 / 339 / 230 459 / 399 / 339
565 / 509 / 459
External Static Pressure (in. wg)
Standard Mode
0.23
0.23
0.23
0.23
0.23
0.23
External Static Pressure (in. wg)
High Mode (Factory Set)
0.31
0.31
0.31
0.31
0.31
0.31
Piping
Liquid Line (in., O.D.)
1/4 Flare
1/4 Flare
1/4 Flare
1/4 Flare
1/4 Flare
3/8 Flare
Vapor Line (in., O.D.)
1/2 Flare
1/2 Flare
1/2 Flare
1/2 Flare
1/2 Flare
5/8 Flare
Condensate Line (in., I.D.)
1
1
1
1
1
1
Table 1: Ducted High Static (BH Frame) Indoor Unit General Data.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes.
This unit comes with a dry nitrogen charge.
All capacities are net with a combination ratio between 95-105%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice. Current certified ratings are available at
www.ahridirectory.org
.
1
Max. power input is rated at maximum setting value.
2
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air
Source Units produced after February 2019.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
4
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
All communication cable to be minimum 18 AWG, 2-conductor, twisted, stranded, shielded
and must comply with applicable local and national codes. Ensure the communication
cable is properly grounded at the master outdoor unit only. Do not ground the ODU-IDU
communication cable at any other point.