4. Trouble Shooting
- 56 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Self-diagnosis Function
1.1 Error Indicator (Indoor)
Ceiling Cassette Type Display
The number of times to blink = Error code
10 degrees
1 degrees
Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
Indoor Error
Code
Title
Cause of Error
1
Air temperature sensor of Indoor unit
Air temperature sensor of indoor unit is
open or short
2
Inlet pipe temperature
Sensor of indoor unit
Inlet pipe temperature sensor of indoor unit
is open or short
3
Communication error : wired remote
controller
↔
indoor unit
Failing to receive wired remote controller
signal in indoor unit PCB
4
Drain pump
Malfunction of drain pump
5
Communication error : outdoor unit
↔
indoor unit
Failing to receive outdoor unit signal in
indoor unit PCB
6
Outlet pipe temperature sensor of indoor
unit
Outlet pipe temperature sensor of indoor
unit is open or short
9
Indoor EEPROM Error
In case when the serial number marked on
EEPROM of Indoor unit is 0 or FFFFFF
10
Abnormal fan motor operation
Disconnecting the fan motor connector/
Failure of indoor fan motor lock