- 34 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Part 2 Functions & Controls
ABNH36GGLA2
Setting Value
Static Pressure[mmAq(Pa)]
4(49)
6(59)
8(78)
10(98)
115
25.9
-
-
-
120
27.9
-
-
-
125
29.9
26.4
-
-
130
32.0
28.5
25.0
-
135
-
30.7
27.5
-
140
-
32.9
29.9
26.0
145
-
-
32.3
28.5
150
-
-
-
31.0
155
-
-
-
-
(Unit: CMM)
ABNH48GRLA2
Setting Value
Static Pressure[mmAq(Pa)]
6(59)
8(78)
10(98)
12(118)
85
31.5
-
-
-
90
36.3
29.8
-
-
95
41.3
34.5
28.4
-
100
45.4
39.7
33.5
27.3
105
-
44.1
38.6
33.1
110
-
-
44.2
38.9
115
-
-
-
44.7
(Unit: CMM)
ABNH42GRLA2
Setting Value
Static Pressure[mmAq(Pa)]
6(59)
8(78)
10(98)
12(118)
85
31.5
-
-
-
90
36.3
29.8
-
-
95
41.3
34.5
28.4
-
100
45.4
39.7
33.5
27.3
105
-
44.1
38.6
33.1
110
-
-
44.2
38.9
115
-
-
-
44.7
(Unit: CMM)
ABNH60GRLA2
Setting Value
Static Pressure[mmAq(Pa)]
6(59)
8(78)
10(98)
12(118)
14(137)
95
41.3
-
-
-
-
100
45.4
39.7
-
-
-
105
49.5 44.1
38.6
-
-
110
-
48.5 44.2
38.9
-
115
-
-
49.8 44.7
42.2
120
-
-
-
50.5 48.1
(Unit: CMM)
Summary of Contents for ABNH09GL1A2