- 31 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
If entering into ESP setup mode by using button, it indicates as
the picture below.
2
Select ESP fan step by pressing button. (01: very low, 02: low,
03: medium, 04: high, 05: very high)
3
Move to ESP value setting by pressing button.
(It is 000 when delivering
from the warehouse.)
4
Press button to setup ESP value.
(It is possible to setup ESP value from 1 to 255,
and 1 is the smallest and 255 is the biggest.)
5
Function code,
ESP code
ESP value
If pressing button long for 3 seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters into user setup mode.
Please press more than 3 seconds for sure.
1
Function Code
ESP value
ESP step
Function code, ESP code
ESP value
Press button to save.
7
Select ESP fan step again by using button and setup ESP value, as
No. 4 and 5, that corresponds each wind flow
6
Press button to exit.
❈
After setup, it automatically gets out of setup mode if there is no button
input for 25 seconds.
❈
When exiting without pressing set button, the manipulated value is not
reflected.
8
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
This is the function that decides the strength of the wind for each wind level and because this function is to make the installation
easier.
• When setting ESP value on the product without very weak wind or power wind function, it may not work.
•
Please be careful not to change the ESP value for each fan step.
•
It does not work to setup ESP value for very low/power step for some products.
•
ESP value is available for specific range belongs to the product.
Part 2 Functions & Controls
Summary of Contents for ABNH09GL1A2
Page 146: ...P NO MFL67478301 December 2013 ...