Control Wiring Termination
This section gives instructions for terminating all types of low voltage inputs.
•
Leviton recommends minimum 18AWG stranded wire for all low voltage wiring
•
Terminate all control wiring directly to the terminal blocks on the printed circuit
board. Use a small 1/8-in. flat screwdriver on these terminals
•
Terminal blocks are 2-part terminals and can be removed for ease of termination.
When reinstalling them make sure they are plugged in the correct direction for the
way they were wired
•
On the 4 relay remote panel, models re4sd-*, inputs #5 & #6, labeled photocell
and occupancy sensors can not be used
•
All control wiring shall be considered Class 2
•
Use control wire type and size as specified below:
Figure 6: Control Wire Type and Size
Input Trigger - What determines an "ON"
Each of the low voltage inputs can be triggered by either the supply of voltage or a
connection to common. When voltage is supplied to an input indicating a change of
state, we call this "pulling up the input" or "active high." When a connection to
common triggers the input, causes a change of state, we call this "pulling down the
input" or "active low."
By default, all inputs are active high (that is receiving voltage to trigger). Active High
inputs must not exceed a n24VDC and must be above +9vdc. Active Low
inputs must connect to the same common at the same potential as the cabinet.
To change from an active high input to an active low input, three things must occur.
First, the polarity jumper must change position. Second, if you intent to use the
output terminals, the polarity IC’s must be changed. Finally, the switch input must be
configured as an "active low" input. The location of the polarity IC’s and the location
of the polarity jumper is shown in figures 5-7 which follow. Information on input
programing is covered in the following sections.
Connector
Type
Wire Size and type
Torque
Switch Inputs
14-24 AWG, Stranded
2 in-lb.
Each product (and in some cases each model of a product) has
a slightly different layout at the terminals blocks. The specific
functions of each terminal is labeled on the circuit board
adjacent to the terminal blocks. When wiring the inputs, verify
that you are connecting the correct wire to the correct terminal
based on function even if it deviates from that shown in this
documentation. Contact our technical services department with
any undocumented questions.
Summary of Contents for EZ-MAX
Page 2: ......
Page 4: ...Page ii...
Page 10: ...Page viii...
Page 16: ...Page 6...
Page 20: ...Page 10...
Page 24: ...Page 14...
Page 26: ...Page 16...
Page 30: ...Page 20...
Page 42: ...Page 32...
Page 44: ...Page 34...
Page 46: ...Page 36...
Page 48: ...Page 38...
Page 54: ...Page 44...
Page 62: ...Page 52...
Page 64: ...Page 54...
Page 74: ...Page 64...
Page 92: ...Page 82...
Page 100: ...Page 90...
Page 112: ...Page 102...
Page 116: ...Page 106...
Page 126: ...Page 116...
Page 132: ...Page 122...
Page 134: ...Page 124...
Page 136: ...Page 126...
Page 164: ...Page 154...
Page 184: ...Page 174...