Page 76
Step 20:
Repeat Steps 8 - 19 as necessary for every button on every station you
are programming.
Step 21:
Assign actions just as for a local switch.
Occupancy Inputs
The process for setting up Occupancy Sensors as inputs to your Z-Max relay cabinet is
identical to low voltage switches except that the type should be defined as
OCC
.
When assigning actions to occupancy inputs, the following three behaviors can be
assigned to the input:
•
NORM ON - AUTO OFF: When the occupancy sensor detects movement and goes
active, relays assigned to this input will turn on only if all relays have been off for
more than the Re-trigger Delay time (set later). Relays will turn off when the
occupancy sensor goes inactive after the Off Delay time (set later). This scenario is
used to hold off reactivating the relays by the sensor when one or more lights has
been manually turned off to temporarily adjust the lighting levels in the room.
•
ALWA ON - AUTO OFF: When the occupancy sensor detects movement and goes
active, relays assigned to this input will turn on. Relays will turn off when the
occupancy sensor goes inactive after the Off Delay time (set later).
•
MAN ON - AUTO OFF: If the input is set to this behavior, the occupancy sensor has
no effect on the relays when it goes active. Instead, the relays must be turned on
via any other means (typically a switch input). When the occupancy switch goes
inactive it will turn off the relays. This application is good for when manual control
is desired from a switch but you want the lights to turn off when someone forgets
to turn them off. This functional operation is required by California Title 24 in most
applications.
Additionally, when setting up occupancy inputs, several additional questions are
asked:
Blink Warn
Indicates whether or not a blink warn should be issued before turning off the lights
associated with this occupancy sensors.
Delay from vacancy until lights off
Allows you to set a delay between when the occupancy sensor indicates that the room
has become vacant and the lights turn off.
Re-trigger Delay
Allows you to set a mandatory delay between when the lights are turned off (by
occupancy sensor or other method) and the earliest point at which the lights can be
turned on, regardless of occupancy state.
OccSen: 3 LOCAL
BLINK WARN: YES
OccSen: 3 LOCAL
BLINK WARN: YES
If the occupancy sensor used already has an
internal delay, the off delay time will be added to
the sensor delay. When using sensors with
internal delay, set delay to 0 (default)
OccSen: 3 LOCAL
RTG DELAY:000sec
Summary of Contents for EZ-MAX
Page 2: ......
Page 4: ...Page ii...
Page 10: ...Page viii...
Page 16: ...Page 6...
Page 20: ...Page 10...
Page 24: ...Page 14...
Page 26: ...Page 16...
Page 30: ...Page 20...
Page 42: ...Page 32...
Page 44: ...Page 34...
Page 46: ...Page 36...
Page 48: ...Page 38...
Page 54: ...Page 44...
Page 62: ...Page 52...
Page 64: ...Page 54...
Page 74: ...Page 64...
Page 92: ...Page 82...
Page 100: ...Page 90...
Page 112: ...Page 102...
Page 116: ...Page 106...
Page 126: ...Page 116...
Page 132: ...Page 122...
Page 134: ...Page 124...
Page 136: ...Page 126...
Page 164: ...Page 154...
Page 184: ...Page 174...