Electrical connection
Leuze electronic
BCL 600i/BCL 601i
36
Termination of the RS 485 interface (BCL 601i)
The device operates as slave in the Leuze multiNet plus network. On the last physical participant, the
Leuze multiNet plus network (RS 485 interface) must be terminated with a terminating resistor (see
chapter 16 "Ordering information and accessories"). This prevents reflections on the Leuze multiNet plus
and improves the immunity to interference.
7.7
Cable lengths and shielding
Observe the following maximum cable lengths and shielding types:
Table 7.7:
Cable lengths and shielding
7.8
Leuze multiNet plus
The Leuze multiNet plus is optimized for fast transmission of scanner data to a primary host computer. The
multiNet plus consists physically of a two-wire RS 485 interface through which the multiNet plus software
protocol is controlled.
This makes wiring the network easy and inexpensive as slaves are looped through to one another in
parallel.
The BCL 600i can only participate as a slave in the Leuze multiNet plus on the BUS OUT socket
and via an external M 12 T-connector (see chapter 7.8.3 and see figure ).
Connection
Interface
Max. cable length
Shielding
BCL – service
USB
3 m
Shielding absolutely
necessary acc. to USB
specifications
BCL – host
RS 232
RS 422
RS 485
10 m
1200 m
1200 m
shielding absolutely
required
RS 422/485 conduc
-
tors, stranded in pairs
Network from the first
BCL to the last BCL
RS 485
1200 m
shielding absolutely
required
RS 485 conductors,
stranded in pairs
BCL – power supply
unit
30 m
Not necessary
Switching input
10 m
Not necessary
Switching output
10 m
Not necessary