Leuze electronic
CMS 700i
– Contour Measurement System
Page 29
6.2 Voltage supply XS1000
6.2.1 Connection details
Supply voltage: 100-230 VAC
Frequency: 50-60 Hz
No-load current: 250 mA
Max. switch-on current: 4 A
6.2.2 Wiring Power supply
Figure 21: Overview
– wiring of the enclosed power plug, protective earth conductor to ground, neutral conductor blue
to 2, phase brown to 1
The fully assembled mains plug must be connected to the XS1000 connection on the bottom of the
LSC-Box control cabinet.
6.3 Connection light curtains
CAUTION
DANGER OF DEATH BY ELECTRIC SHOCK!
Depending on the external wiring, dangerous currents can occur at the outputs!
Ensure that the power supply connection is disconnected during all work and cannot be
accidentally restored!
Only qualified personnel may carry out the electrical installation!
CAUTION
Wiring with at least 3 x 1,5mm
2
Wiring with maximum 3 x 2,5mm
2
CAUTION
Do not make any changes to PLC components in the control cabinet!
Do not make any changes to the file system!
PLC components must be registered in the application software! Leuze electronic is
responsible for the correct interaction of the modules. In case of changes, please contact
the Leuze Service Center!