Troubleshooting
Operating Instructions i510-Cabinet
Error code
Description
Classification
Remedy
Blocking time
[s]
Reset possible
4210
PU: Overtemperature fault
Error
• Check mains voltage.
• Ensure sufficient cooling of the device (heatsink temperature displayed in
P117.01
).
• Clean fan and ventilation slots. Replace fan if necessary.
• Reduce switching frequency (
P305.00
).
0
Yes
4281
Heatsink fan warning
Warning
• Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can
then be removed.
0
Yes
4310
Error: Motor overtemperature
Error
• Check drive dimensions.
5
Yes
6280
Trigger/functions connected incorrectly
Trouble
Check and correct the assignment of the triggers to the functions.
• When keypad or network control is active, the two functions “Inverter enable” (
P400.01
) and “Run” (
P400.02
)
can also be set to “Constant TRUE [1]” to start the motor.
0
Yes
7180
Motor overcurrent
Error
• Check motor load.
• Check drive dimensions.
• Adapt set warning threshold or error threshold to
P353.01
.
1
Yes
9080
Keypad removed
Error
• Plug in the keypad again or activate another control source.
0
Yes
FF06
Motor overspeed
Error
• Adapt the maximum motor speed (
P322.00
) and the warning threshold or error threshold (
P350.01
).
1
Yes
FF37
Automatic start disabled
Error
• Deactivate start command and reset error.
0
Yes
FF85
Keypad full control active
Warning
• Press the keypad key
to exit control mode.
0
Yes