12
Electrical installation
Operating Instructions i510-Cabinet
5.6
Three-phase mains connection 230/240 V
Terminal data, 3-phase 230/240 V
I51AExxxD
I51AExxxD
I51AExxxC
I51AExxxx
I51AExxxD
I51AxxxC
Inverter
[kW]
0.25 ... 0.75
1.1 ... 2.2
4 ... 5.5
0.25 ... 5.5
0.25 ... 2.2
4 ... 5.5
Connection
Mains connection X100
PE connection
Motor connection X105
Connection type
Pluggable screw terminal
Screw terminal
PE screw
Pluggable screw
terminal
Screw terminal
Max. cable cross-section
mm²
2.5
6
6
6
2.5
6
Stripping length
mm
8
8
9
10
8
9
Tightening torque
Nm
0.5
0.7
0.5
2
0.5
0.5
Tools required
0.5 x 3.0
0.6 x 3.5
Torx 20
0.5 x 3.0
0.6 x 3.5
Fusing data/performance data
Inverter
[kW]
0.25
0.37
0.55
0.75
1.1
1.5
2.2
4
5.5
7.5
Rated output current
(heavy duty)
A
1.7
2.4
3.2
4.2
6
7
9.6
16.5
23
-
Max. output current (15s)
A
2.6
3.6
4.8
6.3
9
10.5
14.4
24.8
34.5
-
Rated output current
(light duty)
A
-
-
-
-
-
-
-
-
20.6
27.6
Max. output current (15s)
A
-
-
-
-
-
-
-
-
33
46
Operation without mains choke
Fuse
Characteristic
gG/gL or gRL
-
Max. rated current
A
10
10
16
16
25
25
25
32
32
-
Circuit breaker
Characteristic
B
-
Max. rated current
A
10
10
16
16
25
25
25
32
32
-
Operation with mains choke
Fuse
Characteristic
gG/gL or gRL
Max. rated current
A
10
10
16
16
25
25
25
32
32
32
Circuit breaker
Characteristic
B
Max. rated current
A
10
10
16
16
25
25
25
32
32
32
Earth-leakage circuit breaker
3-phase mains connection
≥ 30 mA, type B
≥ 300 mA, type B
Mains connection
Valid for I51AExxxC inverter.
3/PE
AC 170 V ... 264 V
45 Hz ... 65 Hz
F1
…
F3
Q1
X100
L1
L2
PE
N
L3
L2
3/N/PE
AC 208 V ... 240 V
L3
n.c.
n.c.
Valid for I51AExxxD inverter.
3/PE
AC 170 V ... 264 V
45 Hz ... 65 Hz
F1
…
F3
Q1
X100
L1
L2/N
L3
PE
N
L3
L2
3/N/PE
AC 208 V ... 240 V
Motor connection
X105 U
V
W
Rb1
Rb2
M
3~