10
Electrical installation
Operating Instructions i510-Cabinet
5.3 Control terminals
Basic I/O
Input/output
Terminal X3
Information
Digital inputs
DI1, DI2, DI3, DI4, DI5
DI3/DI4 can be optionally used as frequency or encoder input.
HIGH active/LOW active switchable LOW = 0 ... +3 V, HIGH = +12 V
... +30 V
Digital outputs
DO1
Digital output (max. 100 mA)
Analog inputs
AI1, AI2
Can be optionally used as voltage input or current input.
Analog outputs
AO1
Can be optionally used as voltage output or current output.
10-V output
10 V
Primarily for the supply of a potentiometer (1 ... 10 kΩ). Max.
10 mA
24-V output
24 V
Primarily for the supply of digital inputs. (Max. 100 mA)
Reference potential
GND
Connection system
Plug-in spring terminal
Inverter
[kW]
0.25 ... 15
Connection
Control terminals X3
Connection type
Plug-in spring terminal
Max. cable cross-section
mm²
1.5
Stripping length
mm
9
Tightening torque
Nm
-
Tools required
0.4 x 2.5
Control terminals
5.4 Relay output
The relay is not suitable for direct switching of an electromechanical holding brake. Use a
corresponding suppressor circuit in case of an inductive or capacitive load.
Inverter
[kW]
0.25 ... 15
Connection
Relay output X9
Connection type
Pluggable screw terminal
Max. cable cross-section
mm²
1.5
Stripping length
mm
6
Tightening torque
Nm
0.2
Tools required
0.4 x 2.5
COM
Common contact
NC
Normally-closed contact
NO
Normally-open contact
Max. switching voltage/switching
current
AC 240 V/3 A
DC 24 V/2 A
DC 240 V/0.16 A
Relay output
NC
NO
C
OM
X9
AC 240 V
3 A