20
Commissioning
Operating Instructions i510-Cabinet
Display code
Name
Possible settings/
value ranges
Keypad code
Information
P323.00
Motor current
0.001 ... 1.700 ... 500.000 A *
Setting of the rated motor current according to motor nameplate. With regard to rated motor current (
P323.00
)
P324.00
Max current
0.0 ... 200.0 ... 3000.0 %
Maximum overload current of the inverter.
P400.01
Inverter enable
TRUE
[1]
Assignment of a trigger to the “inverter enable“ function.
Trigger = TRUE: The inverter is enabled (unless there is another cause for inverter disable).
Trigger = FALSE: The inverter is disabled. The motor has no torque and coasts.
P400.02
Run
Digital input 1
[11]
Assignment of a trigger to the “Run” function.
Function 1: Start/stop motor (default setting)
Function 1 is active if no further start commands (start forward/start reverse) have been connected to triggers, no keypad control is active and no
network control is active.
Trigger = TRUE: Let motor rotate forward (CW).
Trigger = FALSE: Stop motor according to stop function (
P203.03
).
Function 2: Start clearance/stop motor
Function 2 is active if further start commands have been connected to triggers, the keypad control is active or the network control is active.
Trigger = TRUE: Start commands of the active control source are enabled.
Trigger = FALSE: Stop motor.
P400.03
Quick stop
Not connected
[0]
Assignment of a trigger to the “Activate quick stop” function.
Trigger = TRUE: Activate quick stop. Quick stop ramp
P225.00
.
Trigger = FALSE: Deactivate quick stop
P400.04
Error reset
Digital input 2
[12]
Assignment of a trigger to the “Reset error” function.
Trigger = FALSE > TRUE (edge): The active error is reset (acknowledged) if the error condition is no longer active and the error is resettable.
Trigger = FALSE: No action.
P400.05
DC braking
Not connected
[0]
Assignment of a trigger to the “Activate DC braking” function.
Trigger = TRUE: Activate DC braking.
Trigger = FALSE: Deactivate DC braking.
P400.06
Start forward
Not connected
[0]
Assignment of a trigger to the “Start forward (CW)” function.
Trigger = FALSE > TRUE (edge): Let motor rotate forward.
Trigger = TRUE > FALSE (edge): No action.Stop via
P400.01
(default setting of digital input 1).
P400.07
Start reverse
Not connected
[0]
Assignment of a trigger to the “Start reverse (CCW)” function.
Trigger = FALSE > TRUE (edge): Let motor rotate backward.
Trigger = TRUE > FALSE (edge): No action.Stop via
P400.01
(default setting of digital input 1).
P400.08
Run forward
Not connected
[0]
Assignment of a trigger to the “Run forward (CW)” function.
Trigger = TRUE: Let motor rotate forward.
Trigger = FALSE: Stop motor.Stop via
P400.01
(default setting of digital input 1).
P400.09
Run reverse
Not connected
[0]
Assignment of a trigger to the “Run reverse (CCW)” function.
Trigger = TRUE: Let motor rotate backward.
Trigger = FALSE: Stop motor.Stop via
P400.01
(default setting of digital input 1).
P400.13
Reverse rot. dir.
Digital input 3
[13]
Assignment of a trigger to the “Reverse rotating direction” function.
Trigger = TRUE: The setpoint specified is inverted (i.e. the sign is inverted).
Trigger = FALSE: No action / deactivate function again.
Default setting = bold print | * Default setting is device-dependent