16
Commissioning
Operating Instructions i510-Cabinet
7.1.3
Quick commissioning - terminal control
The following quick overview with graphical parameter representation is sufficient for
commissioning many applications with terminal control. Further setting options are described
in this document or in the commissioning document.
1. Load default setting = set P700.01 to 1.
2. Set the following parameters for V/f characteristic control:
• Mains voltage P208.01
• V/f characteristic data: Base voltage P303.01
• V/f characteristic data: Base frequency P303.02
• Minimum frequency P210.00
• Maximum frequency P211.00
• Acceleration time 1 P220.00
• Deceleration time 1 P221.00
• Analog input 1: Min frequency value P430.02
• Analog input 1: Max frequency value P430.03
3. Press and hold the key for longer than 3 seconds to save the settings.
7.1.1
Functions of the keys
Key
Actuation
Action
Press briefly
• Navigate in the Menu Change parameters
Press briefly
• Go to Menu/Parameters Confirm parameters
Press and hold for 3s
• Save parameters
• “P.SAVED” in the display indicates that the parameters have been saved
Press briefly
Quit Menu/Parameters
Press briefly
Activate keypad control
Press briefly
Start motor
Press briefly
Change rotating direction
Press briefly
Stop motor
The motor must be at standstill before parameters can be changed or confirmed.
The settings are saved temporarily until the motor is switched off again. Press and hold the
key for 3 s to save the settings permanently.
7.1.2
Example of the keypad handling
Example for DO1 function assignment with parameter P420.02.
GROUP 4
P420.XX
P420.02
I/O setting
Fct. dig. outputs
DO1 func on
P211.00
P430.03
P430.02
P430.02
P2
20
.0
0
P2
21
.00
P210.00
AI1
Time
Fr
eq
ue
ncy