9300 Servo PLC
Appendix
3-25
L
ServoPLC EN 2.0
Code
Info
Possible settings
LCD
Code
Info
Selection
Lenze
LCD
C0357 CE monit time
System bus: Monitoring time for process data input objects
0
{1 msec}
65000
1
3000
CE1monit time
2
3000
CE2monit time
3
3000
CE3monit time
C0358 Reset node
0
System bus: Reset node
0
No function
1
CAN reset node
C0359 CAN state
g
System bus: Status
0
Operational
1
Pre-Operational
2
Warning
3
Bus off
C0360 CAN message
g
System bus: Telegram counter
(number of telegrams)
•
For values > 65535 counting restarts with 0
0
{1 msec}
65535
1
All sent (without free CAN objects)
2
All received (without free CAN objects)
3
Sent to CAN1_OUT
4
Sent to CAN2_OUT
5
Sent to CAN3_OUT
6
Sent to parameter channel 1
7
Sent to parameter channel 2
8
Received by CAN1_IN
9
Received by CAN2_IN
10
Received by CAN3_IN
11
Received from parameter channel 1
12
Received from parameter channel 2
C0361 Load IN/OUT
g
System bus: Bus load
•
Trouble-free operation demands that the total bus load
(all connected devices) does not exceed 80 %.
0
{1 %}
100
1
All sent (without free CAN objects)
2
All received (without free CAN objects)
3
Sent to CAN1_OUT
4
Sent to CAN2_OUT
5
Sent to CAN3_OUT
6
Sent to parameter channel 1
7
Sent to parameter channel 2
8
Received by CAN1_IN
9
Received by CAN2_IN
10
Received by CAN3_IN
11
Received from parameter channel 1
12
Received from parameter channel 2
C0362 Sync cycle
g
System bus: Time between two sync telegrams
(in preparation)
1
{1 msec}
30
C0363 Sync corr
1
System bus: Sync correction increments
1
0.2
µ
s/ms
2
0.4
µ
s/ms
3
0.6
µ
s/ms
4
0.8
µ
s/ms
5
1.0
µ
s/ms