6
13433283_P94MI01D_EN
Technical Data
2.2
Connections and I/O
2.2.1
P1 - Input Power (Mains) Connection
Standard Models
1
2
3
4
L3
L2
L1
PE
Doubler Models
1
2
3
4
L2/N
L1
N
PE
Pin Name Function
Name Function
1
PE
Protective Earth (Ground)
PE
Protective Earth (Ground)
2
L1
AC Power in
N
AC Power Neutral (120V Doubler only)
3
L2
AC Power in
L1
AC Power in
4
L3
AC Power in (3~ models only)
L2/N AC Power in (non-doubler operation)
Fuse
PE
L1, L2, L3
EN 60204
UL
Type
[A]
1~/3~
[A]
1~/3~
[A]
1~/3~
[mm
2
]
[AWG]
[mm]
[in]
[Nm]
[lb-in]
[mm
2
]
[AWG]
1~/3~
[mm]
[in]
[Nm]
[lb-in]
E94_020S1N_~
M20/M10
C20/C10
20/10
2.5
14
6
0.25
0.5
4.5
2.5/2.5
14/14
6
0.25
0.5
4.5
E94_040S1N_~
M32/M20
C32/C20
30/20
4
12
4/2.5
12/14
E94_020S2F_~
M20
C20
20
2.5
14
6
0.25
0.5
4.5
2.5
14
6
0.25
0.5
4.5
E94_040S2F_~
M20
C20
20
E94_080S2F_~
M32
C32
32
4
12
4
12
E94_100S2F_~
M40
C40
40
6
10
6
10
E94_020Y2N_~
M20/M16
C20/C16
20/15
2.5
14
6
0.25
0.5
4.5
2.5/2.5
14/14
6
0.25
0.5
4.5
E94_040Y2N_~
M20/M16
C20/C16
20/15
E94_080Y2N_~
M32/M20
C32/C20
30/20
4
12
4/2.5
12/14
E94_100Y2N_~
M32/M20
C32/C20
30/20
6
10
6/2.5
10/14
0.79
7
E94_120Y2N_~
M50/M32
C50/C32
50/30
6
10
6/4
10/12
0.5
4.5
E94_180T2N_~
M40
C40
40
6
10
0.79
7
6
10
0.79
7
E94_020T4N_~
M10
C10
10
2.5
14
6
0.25
0.5
4.5
2.5
14
6
0.25
0.5
4.5
E94_040T4N_~
M10
C10
10
E94_060T4N_~
M20
C20
20
E94_090T4N_~
M25
C25
25
1)
Installations with high fault current due to large supply mains may require a type D circuit breaker.
2)
UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN, JJS or equivalent.
3)
Thermal-magnetic type breakers preferred.
WARNING!
The PositionServo drive runs on phase-to-phase voltage. For the standard drive, either a delta or wye transformer may be used for
3-phase input. However, for reinforced insulation of user accessible I/O circuits, each phase voltage to ground must be less than or
equal to 300VAC rms. This means that the power system must use center grounded wye secondary configuration for 400/480VAC
mains.
STOP!
For the E94 _020S1N_~ and E94_040S1N_~ doubler models, do NOT apply 240VAC to the N and L1 terminals. Severe damage to
the drive will result.
1)
2)
3)