or replacement of servers or parts on implementation of appropriate remedial measures to mitigate such
environmental contamination. Implementation of such remedial measures is a customer responsibility.
Table 31. Limits for particulates and gases
Contaminant
Limits
Particulate
• The room air must be continuously filtered with 40% atmospheric dust spot efficiency
(MERV 9) according to ASHRAE Standard 52.2
1
.
• Air that enters a data center must be filtered to 99.97% efficiency or greater, using
high-efficiency particulate air (HEPA) filters that meet MIL-STD-282.
• The deliquescent relative humidity of the particulate contamination must be more than 60%
2
.
• The room must be free of conductive contamination such as zinc whiskers.
Gaseous
• Copper: Class G1 as per ANSI/ISA 71.04-1985
3
• Silver: Corrosion rate of less than 300 Å in 30 days
1
ASHRAE 52.2-2008 -
Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle
Size
. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
2
The deliquescent relative humidity of particulate contamination is the relative humidity at which the dust absorbs
enough water to become wet and promote ionic conduction.
3
ANSI/ISA-71.04-1985.
Environmental conditions for process measurement and control systems: Airborne
contaminants
. Instrument Society of America, Research Triangle Park, North Carolina, U.S.A.
Compliance with Republic of Turkey Directive on the Restriction of
Hazardous Substances
Meets requirements of the Republic of Turkey Directive on the Restriction of the Use of Certain Hazardous
Substances In Electrical and Electronic Equipment (EEE).
Battery return program
This product may contain a lithium or lithium ion battery. Consult your user manual or service manual for
specific battery information. The battery must be recycled or disposed of properly. Recycling facilities may
not be available in your area. For information on disposal or batteries outside the United States, go to
http://www.lenovo.com/lenovo/environment or contact your local waste disposal facility.
170
ThinkServer TD230 Hardware Maintenance Manual
Summary of Contents for and 1040
Page 1: ...ThinkServer TD230 Hardware Maintenance Manual Machine Types 1027 1029 1039 and 1040 ...
Page 2: ......
Page 3: ...ThinkServer TD230 Hardware Maintenance Manual Machine Types 1027 1029 1039 and 1040 ...
Page 16: ...10 ThinkServer TD230 Hardware Maintenance Manual ...
Page 20: ...14 ThinkServer TD230 Hardware Maintenance Manual ...
Page 44: ...38 ThinkServer TD230 Hardware Maintenance Manual ...
Page 148: ...142 ThinkServer TD230 Hardware Maintenance Manual ...
Page 166: ...160 ThinkServer TD230 Hardware Maintenance Manual ...
Page 168: ...162 ThinkServer TD230 Hardware Maintenance Manual ...
Page 172: ...166 ThinkServer TD230 Hardware Maintenance Manual ...
Page 185: ......