background image

www.lennoxemea.com

PCUS Thermostat - User Manual - 0821EN

11

3. LOGICAL DESCRIPTION OF THE PCUS REMOTE CONTROL

3.1 VENTILATION REGULATION

The PCUS control card is suitable for regulating units with standard three-speed fans or as an alternative to regulating 
the ventilation of units with EC fans.
The configuration of the type of fans is fixed at the manufacturer parameter level. In the case of standard three-
speed fans, three 230V digital outputs are used, while in the case of EC fans, two 0-10V analog outputs are used. 
For standard fans, the ventilation is adjusted by pressing the ventilation button which allows the passage from one 
speed to the next.
For EC fans, regulation is always carried out by pressing the ventilation button, which however correspond to different 
voltages that correspond to the minimum, average and maximum voltage that can be set in the manufacturer 
parameters.
These values are by default 1V and 10V, i.e. the minimum speed corresponds to 1V, the average to 5.5V and the 
maximum to 10V.
The minimum and maximum values of the supply fan correspond to parameters L0.9 and L0.A of the manufacturer 
parameters, while the minimum and maximum values of the return fan correspond to parameters L0.B and L0.C 
of the manufacturer parameters.If it is necessary to have different voltage values with the same speed selected, 
it is possible to modify the minimum and maximum values of one of the two fans and the speed values will adapt 
according to these limits according to the following rule: low speed = V minimum medium speed = (V m 
V maximum) / 2 high speed = V maximum
For EC fans it is also possible to adjust the operation in accordance with an external analogue CO2, RH, VOC probe 
equipped with a 0-10V output. Depending on the type of sensor used, it is possible to set the reference set value 
and a regulation band within which the ventilation moves within the minimum and maximum values set.

3.2 TEMPERATURE REGULATION

Temperature regulation. if there are active devices, such as water valve or electric heater, it is activated by setting 
the desired set point with the + or - keys.
The control probe is by default the room temperature probe, however it is possible to select the inlet air probe by 
modifying the manufacturer parameter L0.6 from 0 to 1.
The adjustment can be: only hot, only cold, hot and cold.
In the case of heating only adjustment, the 10C icon will be lit and the actual activation of the water valve or the 
electric heating element will be highlighted by the lighting of icons 4C or 4D.
In the case of cooling only regulation, the 10B icon will be lit and the actual activation of the cooling water valve 
will be highlighted by the 4C icon lighting up.
In the case of hot and cold adjustment, the 10 ° icon will light up and the adjustment described in the paragraphs 
above will be active at the same time for only hot and cold only adjustment.
In the case of regulation with mixed valve, it is not possible to regulate hot and cold at the same time, but only hot 
and cold only settings are manually selectable.
The temperature regulation applies by default an energy saving logic that takes into account the external temperature 
and therefore, if this allows it, the water valve or the electric heater is not activated if the external air temperature 
conditions do not require it.
It is possible to exclude the influence of the external air temperature from the hot regulation logic by modifying 
the manufacturer parameter L0.3 by setting it to 1.
It is possible to exclude the influence of the external air temperature from the cold regulation logic by modifying 
the manufacturer parameter L0.4 by setting it to 1.
In the case of temperature regulation with modulating water valve (V3M) it is possible to define the temperature 
regulation band with respect to the set with user parameter U0.6.
For example, with U0.6 = 2 °C, the maximum opening of the water valve will occur when the difference between the 
desired set point and the detected temperature is equal to or greater than this value, while it acts in a proportional 
way to this difference when it is included. within 2 °C.

3.3 OPERATION OF HEAT RECOVERY DEFROST

The recovery defrost action is possible if the unit is equipped with the expulsion temperature probe.
If the expulsion temperature drops below parameter U0.4, the defrosting action is activated and ends when the 
expulsion temperature rises above U0.4 + U0.5.
The defrost action can take place in three ways that can be set in parameter U0.9.
U0.9 = 1 speed reduction of the EC fans
U0.9 = 2 closing of the inlet / outlet air dampers and opening of recirculation damper (only with unit equipped 
with these dampers)
U0.9 = 4 activation of the electrical preheating resistance.

Summary of Contents for PCUS

Page 1: ...CUS Thermostat User Manual Before starting to work with the machine operation read the installation use and maintenance manual PCUS PCUSM Thermostat User manual Installation use and maintenance manual...

Page 2: ...ATURE REGULATION 3 3 OPERATION OF HEAT RECOVERY DEFROST 3 5 AIR INLET OUTLET DAMPER OPERATION 3 6 FREE HEATING COOLING LOGIC OPERATION 3 7 DIRTY FILTER INLET SIGNAL 3 8 REMOTE ON OFF SIGNAL 3 9 EXTERN...

Page 3: ...self 1 COMPOSITION OF PCUS CONTROLLER 1 1 PCUS UNIT The PCUS control system consists of two parts an LCD display and setting and a control unit which contains the interface relays to be connected to t...

Page 4: ...Button 2 Mode Button 3 Ventilation Button 4 Button 5 Button 6 Ventilation Symbol Area Graphical Area 1 Probe indicator displayed on line 2 2 Room temperature and fan icons display 3 Visualization of r...

Page 5: ...and the key 5 allow you to modify the temperature set point 2 6 ELECTRICAL CONNECTION Refer to the attached connection diagram 2 7 PCUS DESCRIPTION The PCUS control system is a thermostat capable of c...

Page 6: ...mode adjustment is envisaged this mode will be fixed with the 10C icon always active and pressing the Mode key will have no effect Similarly if at the manufacturer level only adjustment in cold mode i...

Page 7: ...set for week 1 which identifies the days from Monday to Friday week 6 which identifies Saturday and week 7 which identifies Sunday The following can be selected ventilation speed temperature set poin...

Page 8: ...values and temperature The photo below shows what is indicated in this point 12 Press the Mode key to switch to the setting of band 1 on Saturday identified by the wording Week 6 and set the desired...

Page 9: ...firming all the previously set values by pressing the Mode button several times 22 Change the setting of the desired action from ON to OFF with the or keys The photo below shows what is indicated in t...

Page 10: ...the and keys and then press M to confirm the values The user parameters table is shown below Meaning U0 0 Temperature set point C min 15 max 35 U0 1 Temperature differential C min 0 max 5 U0 2 Antifre...

Page 11: ...0 6 from 0 to 1 The adjustment can be only hot only cold hot and cold In the case of heating only adjustment the 10C icon will be lit and the actual activation of the water valve or the electric heati...

Page 12: ...be activated when the contact is opened The activation of the dirty filters function activates the signal given by the 4th icon however by default it does not perform any action allowing normal operat...

Page 13: ...return air fan speed 1 9 V 40004 R W L0 c Maximum return air fan speed da L0 9 10 V 40016 R W U0 0 Set temperature 15 0 35 0 C 40017 R W U0 1 Temperature differential 0 0 5 0 C 40018 R W U0 2 Antifree...

Page 14: ...to the electronic board before proceeding with the modification The following table shows the meaning of the DIP switches NUMBER MEANING VALUE 1 Unit with three speed fans 0 NO 1 YES 2 Unit with EC fa...

Page 15: ...mmitment to quality the specifications ratings and dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance ca...

Reviews: