3.4 ANTIFREEZE  OPERATION

The anti-freeze protection function is intended to prevent the formation of ice on the water coil (if the unit is 
equipped with a water coil).
The function is activated when the contact opens on a digital input suitably configured by manufacturer parameters.
If digital input 2 is used, set L1.3 = 2 and L1.4 = 1, if digital input 3 is used, L1.5 = 2 and L1.6 = 1 must be set.When the 
protection intervenes, the fans are turned off, the air inlet / outlet shutters closed and the water valve is activated, 
whether it is on / off or modulating (if heating mode is selected).

3.5 AIR INLET / OUTLET  DAMPER OPERATION

The PCUS control is able to operate air inlet / outlet dampers equipped with on / off servocontrol.When the unit is 
switched on, the shutter opening signal is activated and after a settable waiting time the fans are switched on.The 
waiting time can be set by user parameter U0.7 in an admissible range between 0 and 180 seconds.

3.6 FREE HEATING / COOLING  LOGIC OPERATION

The operating logic provides for the activation of an on / off type output for the activation of the recovery bypass.
The activation of this output occurs when the external air conditions allowit.If the outside air temperature is higher 
than the desired set and the room temperature is lower than the desired set, the free heating function is activated.
If the outside air temperature is lower than the desired set and the ambient temperature is higher than the desired 
set, the free cooling function is activated.
To avoid oscillations of the bypass there is a differential defined by parameter U0.2 which by default is set at + 1 ° C.

3.7 DIRTY FILTER INLET SIGNAL

The PCUS control has an on / off type input for the dirty filter signal. The preset input is DI1 and by default the dirty 
filters function is activated when the input contact is closed.
The manufacturer parameter L1.1 equal to 1 activates the dirty filters function, while the parameter L1.2 allows to 
invert the logic of the signal.
L1.2 equal to 0 causes the dirty filters signal to be activated when the contact is closed, L1.2 par to 1 causes the 
signal to be activated when the contact is opened.
The activation of the dirty filters function activates the signal given by the 4th icon, however by default it does not 
perform any action allowing normal operation of the fans, if instead you want the dirty filters functionality to stop 
the ventilation, the manufacturer parameter must be set to 1 L0.2.

3.8 REMOTE ON/OFF SIGNAL

Remote switching on / off of the unit with the help of an external switch is possible using the DI2 input by setting the 
manufacturer parameter L1.3 = 1, while the manufacturer parameter L1.4 inverts the contact logic.With L1.4 = 0 the 
ignition of the unit occurs with closed contact, while with L1.4 = 1 the ignition occurs with open contact.If remote on
/ off is selected, it overrides the on / off button on the display, ie if the unit is turned off from the display it turns 
on again immediately, and vice versa if it is turned on it turns off immediately.

3.9 EXTERNAL ALARM INPUT

The external alarm function is possible with the aid of a digital input (DI3), which allows the immediate stop of the 
ventilation.Use only a clean contact for this function, which can be activated by setting the manufacturer parameter 
L1.5 = 3.

3.10 ALARM OR UNIT SIGNAL OUTPUT ON

It is possible to use a digital voltage output (230V ac) to interface with external devices for two possible functions 
of alarm present or unit on. For example, to use output DO1 as an alarm present, the manufacturer parameter L2.1 = 
4 must be set and L2.2 allows the logic to be inverted, with L2.2 = 0 the output will be active if there are no alarms 
and will be disabled if there are alarms while with L2.1 =
1 the output will be active if there are alarms and deactivate with no alarms.
If the DO1 output is already intended for another use, the same functionality is possible with one of the other outputs 
on the controller.Again as an example, in order to use the DO1 output as an On unit, parameter L2.1 = 3 must be set 
and L2.2 allows you to invert the operating logic as specified for the example above.

3.11 NOTE ON MANUFACTURER PARAMETERS

The manufacturer parameters allow to modify the functionality of all the inputs and outputs of the device and if 
not correctly set they can compromise the regular operation of the unit, for this reason it is absolutely necessary 
to avoid their modification other than what is not expressly reported here.

Summary of Contents for PCUS

Page 1: ...CUS Thermostat User Manual Before starting to work with the machine operation read the installation use and maintenance manual PCUS PCUSM Thermostat User manual Installation use and maintenance manual...

Page 2: ...ATURE REGULATION 3 3 OPERATION OF HEAT RECOVERY DEFROST 3 5 AIR INLET OUTLET DAMPER OPERATION 3 6 FREE HEATING COOLING LOGIC OPERATION 3 7 DIRTY FILTER INLET SIGNAL 3 8 REMOTE ON OFF SIGNAL 3 9 EXTERN...

Page 3: ...self 1 COMPOSITION OF PCUS CONTROLLER 1 1 PCUS UNIT The PCUS control system consists of two parts an LCD display and setting and a control unit which contains the interface relays to be connected to t...

Page 4: ...Button 2 Mode Button 3 Ventilation Button 4 Button 5 Button 6 Ventilation Symbol Area Graphical Area 1 Probe indicator displayed on line 2 2 Room temperature and fan icons display 3 Visualization of r...

Page 5: ...and the key 5 allow you to modify the temperature set point 2 6 ELECTRICAL CONNECTION Refer to the attached connection diagram 2 7 PCUS DESCRIPTION The PCUS control system is a thermostat capable of c...

Page 6: ...mode adjustment is envisaged this mode will be fixed with the 10C icon always active and pressing the Mode key will have no effect Similarly if at the manufacturer level only adjustment in cold mode i...

Page 7: ...set for week 1 which identifies the days from Monday to Friday week 6 which identifies Saturday and week 7 which identifies Sunday The following can be selected ventilation speed temperature set poin...

Page 8: ...values and temperature The photo below shows what is indicated in this point 12 Press the Mode key to switch to the setting of band 1 on Saturday identified by the wording Week 6 and set the desired...

Page 9: ...firming all the previously set values by pressing the Mode button several times 22 Change the setting of the desired action from ON to OFF with the or keys The photo below shows what is indicated in t...

Page 10: ...the and keys and then press M to confirm the values The user parameters table is shown below Meaning U0 0 Temperature set point C min 15 max 35 U0 1 Temperature differential C min 0 max 5 U0 2 Antifre...

Page 11: ...0 6 from 0 to 1 The adjustment can be only hot only cold hot and cold In the case of heating only adjustment the 10C icon will be lit and the actual activation of the water valve or the electric heati...

Page 12: ...be activated when the contact is opened The activation of the dirty filters function activates the signal given by the 4th icon however by default it does not perform any action allowing normal operat...

Page 13: ...return air fan speed 1 9 V 40004 R W L0 c Maximum return air fan speed da L0 9 10 V 40016 R W U0 0 Set temperature 15 0 35 0 C 40017 R W U0 1 Temperature differential 0 0 5 0 C 40018 R W U0 2 Antifree...

Page 14: ...to the electronic board before proceeding with the modification The following table shows the meaning of the DIP switches NUMBER MEANING VALUE 1 Unit with three speed fans 0 NO 1 YES 2 Unit with EC fa...

Page 15: ...mmitment to quality the specifications ratings and dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance ca...

Reviews: