5. DIP SWITCH
5.1 DIP SWITCH POSITIONING
There are sixteen DIP switches on the control board.
Generally the position of the DIP switches is set during the unit construction phase and therefore it is not necessary
to change the assigned positions.
If it is necessary to change the position of one or more DIP switches, it is imperative to disconnect the power supply
to the electronic board before proceeding with the modification.
The following table shows the meaning of the DIP switches.
NUMBER
MEANING
VALUE
1
Unit with three speed fans
0 = NO 1 = YES
2
Unit with EC fans
0 = NO 1 = YES
3
Type of antifreeze
0 = Digital - 1 = Analogic
4
Heating/cooling valves
0 = On/Off / 1 = Modulating
5
Heating type
0 = Water valve / 1 = Electric heater
6
Air inlet presence / Expulsion dampers
0 = NO 1 = YES
7
Presence of FH/FC damper
0 = NO 1 = YES
8
AI5 sensor presence
0 = NO 1 = YES
set-16
Modbus address (PCUSM reserved)
From 1 to 244 (least significant 9-bit DIP switch, most
significant 16-bit DIP switch) / Example: 00000001
address 1