Troubleshooting
Electrical Control System
142
2.4.4.11. P4 Malfunction
The troubleshooting is same as the “
IPM module protection
”
2.4.4.12. J0 Malfunction
Malfunction conditions
When evaporator coil temperature is more than 60°C, the unit stops. It
starts again only when the evaporator coil temperature is less than
54°C
Possible causes
•
Faulty evaporator coil temperature sensor
•
Dirty heat exchanger
•
Faulty fan
•
Faulty PCB
J0 displayed
J0 displayed
Evaporator high temperature protection
Evaporator high temperature protection
Is the compressor operating?
Is the compressor operating?
Yes
Is the outdoor ambient
temperature is higher than 30
℃
?
Is the outdoor ambient
temperature is higher than 30
℃
?
No
Correct the connection
Correct the connection
No
Is the connection
between T2 and The
PCB is in working order?
Have T2 and T2B been
reversed?
Is the connection
between T2 and The
PCB is in working order?
Have T2 and T2B been
reversed?
Is the resistance of T2
normal according to
Appendix
1?
Is the resistance of T2
normal according to
Appendix
1?
Replace the temperature sensor
Replace the temperature sensor
No
Yes
Yes
Stop the unit
Stop the unit
Yes
Is the air-outlet blocked?
Is the air-outlet blocked?
Are the heat exchanger and
filter dirty
?
Are the heat exchanger and
filter dirty
?
Is the indoor fan running
normally?
Is the indoor fan running
normally?
No
Yes
Clean the air-outlet
Clean the air-outlet
Replace the indoor main
PCB
Replace the indoor main
PCB
Clean the heat exchanger and filter
Clean the heat exchanger and filter
Yes
No
Yes
Refer to the solution for the
malfunction of the fan speed being out
of control . Find the cause and resolve
the problem
Refer to the solution for the
malfunction of the fan speed being out
of control . Find the cause and resolve
the problem
No
No
Summary of Contents for LICH4012021T431E-1
Page 12: ...Service Space Indoor Units 10 3 Service Space 1000mm 1000mm 1000mm 1000m m Chart 3...
Page 13: ...Wiring Diagrams Indoor Units 11 4 Wiring Diagrams...
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 36K Cooling Heating...
Page 16: ...Air Velocity Distributions Reference Data Indoor Units 14 48 60K Cooling Heating...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring...
Page 28: ...Wiring Diagrams Indoor Units 26 4 Wiring Diagrams 12k 18k 60k...
Page 39: ...Field Wiring Indoor Units 37 10 Field Wiring 12K 18K 60K...
Page 43: ...Ceiling Floor Type Indoor Units 41 3 Service Space...
Page 48: ...Ceiling Floor Type Indoor Units 46 Floor installation Discharge angle 17 Discharge angle 50...
Page 50: ...Ceiling Floor Type Indoor Units 48 Floor installation Discharge angle 17 Discharge angle 50...
Page 52: ...Ceiling Floor Type Indoor Units 50 Floor installation Discharge angle 17 Discharge angle 50...
Page 54: ...Field Wiring Indoor Units 52 10 Field Wiring...
Page 57: ...Features Indoor Units 55...
Page 59: ...Service Space Indoor Units 57 3 Service Space...
Page 60: ...Wiring Diagrams Indoor Units 58 4 Wiring Diagrams LICH4012021T431E 1 LICH4018021T431E...
Page 64: ...Field Wiring Indoor Units 62 10 Field Wiring LICH4012021T431E 1 LICH4018021T431E...
Page 67: ...Dimensions Outdoor Units 65 Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404...
Page 69: ...Wiring Diagrams Outdoor Units 67 3 Wiring Diagrams LIHP012000T431E...
Page 70: ...Wiring Diagrams Outdoor Units 68 LIHP018000T431E LIHP024000T431E...
Page 71: ...Wiring Diagrams Outdoor Units 69 LIHP036000T431E...
Page 72: ...Wiring Diagrams Outdoor Units 70 LIHP036000M431E...
Page 73: ...Wiring Diagrams Outdoor Units 71 LIHP048000T431E LIHP048000M431E LIHP060000M431E...
Page 98: ...Refrigerant pipe installation Installation 96...