Troubleshooting
Electrical Control System
129
2.4.3 Units with TWINS Function (for the Super-Slim Cassette )
2.4.3.1 Communication
Malfunction
between Master Unit and Indoor Unit
F3 Displayed
F3 Displayed
Communication failure between
master unit and slave unit
Communication failure between
master unit and slave unit
Check the dial switch settings of
master unit and slave unit. Are they
correct?
Check the dial switch settings of
master unit and slave unit. Are they
correct?
Correct the
settings
Correct the
settings
No
Check the PQE communication wires
connection, is it wired properly?
Check the PQE communication wires
connection, is it wired properly?
Yes
Correct the wire
connections
Correct the wire
connections
No
One of the 2 indoor PCBs is defective.
Connect only one indoor unit to the outdoor
unit separately. The one that displays an E1
error code is defective
One of the 2 indoor PCBs is defective.
Connect only one indoor unit to the outdoor
unit separately. The one that displays an E1
error code is defective
Yes
2.4.3.2 Other Malfunction between Master Unit and Indoor Unit
One indoor unit displays ”E9”, which means the other indoor unit is faulty. Check the other indoor unit’s error
code and then follow the prescribed solutions to resolve the malfunction.
E8
Summary of Contents for LICH4012021T431E-1
Page 12: ...Service Space Indoor Units 10 3 Service Space 1000mm 1000mm 1000mm 1000m m Chart 3...
Page 13: ...Wiring Diagrams Indoor Units 11 4 Wiring Diagrams...
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 36K Cooling Heating...
Page 16: ...Air Velocity Distributions Reference Data Indoor Units 14 48 60K Cooling Heating...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring...
Page 28: ...Wiring Diagrams Indoor Units 26 4 Wiring Diagrams 12k 18k 60k...
Page 39: ...Field Wiring Indoor Units 37 10 Field Wiring 12K 18K 60K...
Page 43: ...Ceiling Floor Type Indoor Units 41 3 Service Space...
Page 48: ...Ceiling Floor Type Indoor Units 46 Floor installation Discharge angle 17 Discharge angle 50...
Page 50: ...Ceiling Floor Type Indoor Units 48 Floor installation Discharge angle 17 Discharge angle 50...
Page 52: ...Ceiling Floor Type Indoor Units 50 Floor installation Discharge angle 17 Discharge angle 50...
Page 54: ...Field Wiring Indoor Units 52 10 Field Wiring...
Page 57: ...Features Indoor Units 55...
Page 59: ...Service Space Indoor Units 57 3 Service Space...
Page 60: ...Wiring Diagrams Indoor Units 58 4 Wiring Diagrams LICH4012021T431E 1 LICH4018021T431E...
Page 64: ...Field Wiring Indoor Units 62 10 Field Wiring LICH4012021T431E 1 LICH4018021T431E...
Page 67: ...Dimensions Outdoor Units 65 Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404...
Page 69: ...Wiring Diagrams Outdoor Units 67 3 Wiring Diagrams LIHP012000T431E...
Page 70: ...Wiring Diagrams Outdoor Units 68 LIHP018000T431E LIHP024000T431E...
Page 71: ...Wiring Diagrams Outdoor Units 69 LIHP036000T431E...
Page 72: ...Wiring Diagrams Outdoor Units 70 LIHP036000M431E...
Page 73: ...Wiring Diagrams Outdoor Units 71 LIHP048000T431E LIHP048000M431E LIHP060000M431E...
Page 98: ...Refrigerant pipe installation Installation 96...