Troubleshooting
Electrical Control System
140
P0 displayed
P0 displayed
IPM module protection
IPM module protection
Yes
Is the power voltage normal?
Is the power voltage normal?
Is the outdoor terminal voltage
normal
?
Is the outdoor terminal voltage
normal
?
Restart the unit when the power supply
returns to normal
Restart the unit when the power supply
returns to normal
No
Yes
No
Reconnect the power
wires
Reconnect the power
wires
Yes
Is the voltage between L and N
normal
?
Is the voltage between L and N
normal
?
Yes
Is the input voltage of bridge
rectifier normal
?
Is the input voltage of bridge
rectifier normal
?
No
No
Are the power wires
connected properly?
Are the power wires
connected properly?
Reconnect L and N
Reconnect L and N
Are L and N wired
correctly?
Are L and N wired
correctly?
Reconnect the bridge
rectifier
Reconnect the bridge
rectifier
Is the bridge rectifier
properly wired?
Is the bridge rectifier
properly wired?
No
No
Yes
Replace the PFC module(If This has not been
done already)
Replace the PFC module(If This has not been
done already)
No
Is the voltage between P and
N properly wired according to
Appendix
3
?
Is the voltage between P and
N properly wired according to
Appendix
3
?
Replace the bridge rectifier
Replace the bridge rectifier
No
Is the bridge rectifier
operating normally?
Is the bridge rectifier
operating normally?
Are the reactor or
Inductance wired properly?
Are the reactor or
Inductance wired properly?
Reconnect the wiring
Reconnect the wiring
No
Are the reactor or
inductance normal?
Are the reactor or
inductance normal?
Yes
Replace reactor or
inductance
Replace reactor or
inductance
No
Is the connecting wire between
the main board and the IPM
board connected tightly?
Is the connecting wire between
the main board and the IPM
board connected tightly?
Reconnect the main board and
IPM board
Reconnect the main board and
IPM board
No
Is the outdoor unit ventilation
in working order?
Is the outdoor unit ventilation
in working order?
Yes
Make sure that the outdoor unit is
ventilating properly
Make sure that the outdoor unit is
ventilating properly
Check whether the refrigerant system is in
working order
Check whether the refrigerant system is in
working order
No
Is the outdoor fan running
properly?
Is the outdoor fan running
properly?
Refer to the solution for themalfunction
of the fan speed being out of control .
Find the cause and resolve the problem
Refer to the solution for themalfunction
of the fan speed being out of control .
Find the cause and resolve the problem
No
Yes
No
Yes
Yes
Is the compress is running
normally?
Is the compress is running
normally?
Yes
Replace the compressor
Replace the compressor
No
Replace IPM Board. Is the problem
resolved?
Replace IPM Board. Is the problem
resolved?
Replace the outdoor main PCB. Is
the problem resolved?
Replace the outdoor main PCB. Is
the problem resolved?
No
Is the connecting wire of the
compressor is connected correctly
or tightly
Is the connecting wire of the
compressor is connected correctly
or tightly
Reconnect he connecting wire
of the compressor
Reconnect he connecting wire
of the compressor
No
Yes
Yes
Summary of Contents for LICH4012021T431E-1
Page 12: ...Service Space Indoor Units 10 3 Service Space 1000mm 1000mm 1000mm 1000m m Chart 3...
Page 13: ...Wiring Diagrams Indoor Units 11 4 Wiring Diagrams...
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 36K Cooling Heating...
Page 16: ...Air Velocity Distributions Reference Data Indoor Units 14 48 60K Cooling Heating...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring...
Page 28: ...Wiring Diagrams Indoor Units 26 4 Wiring Diagrams 12k 18k 60k...
Page 39: ...Field Wiring Indoor Units 37 10 Field Wiring 12K 18K 60K...
Page 43: ...Ceiling Floor Type Indoor Units 41 3 Service Space...
Page 48: ...Ceiling Floor Type Indoor Units 46 Floor installation Discharge angle 17 Discharge angle 50...
Page 50: ...Ceiling Floor Type Indoor Units 48 Floor installation Discharge angle 17 Discharge angle 50...
Page 52: ...Ceiling Floor Type Indoor Units 50 Floor installation Discharge angle 17 Discharge angle 50...
Page 54: ...Field Wiring Indoor Units 52 10 Field Wiring...
Page 57: ...Features Indoor Units 55...
Page 59: ...Service Space Indoor Units 57 3 Service Space...
Page 60: ...Wiring Diagrams Indoor Units 58 4 Wiring Diagrams LICH4012021T431E 1 LICH4018021T431E...
Page 64: ...Field Wiring Indoor Units 62 10 Field Wiring LICH4012021T431E 1 LICH4018021T431E...
Page 67: ...Dimensions Outdoor Units 65 Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404...
Page 69: ...Wiring Diagrams Outdoor Units 67 3 Wiring Diagrams LIHP012000T431E...
Page 70: ...Wiring Diagrams Outdoor Units 68 LIHP018000T431E LIHP024000T431E...
Page 71: ...Wiring Diagrams Outdoor Units 69 LIHP036000T431E...
Page 72: ...Wiring Diagrams Outdoor Units 70 LIHP036000M431E...
Page 73: ...Wiring Diagrams Outdoor Units 71 LIHP048000T431E LIHP048000M431E LIHP060000M431E...
Page 98: ...Refrigerant pipe installation Installation 96...