Page 22
LGM/LCM156, 180, 210, 240, 300
TABLE 10
210 Reheat Compressor 1 Frequency 48Hz - 581019-01
Outdoor
Coil En
tering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Dis
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc.
+5
psig
65°F
245
127
267
126
241
120
264
141
75°F
279
130
303
129
279
129
301
146
85°F
317
133
344
132
318
136
342
149
95°F
367
136
393
134
365
143
391
152
105°F
407
139
438
138
409
147
438
155
115°F
461
143
492
141
462
151
493
159
TABLE 11
240 Std. Compressor 1 Frequency 62Hz - 581020-01
Outdoor
Coil En
tering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Dis
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc.
+5
psig
65°F
250
117
261
124
252
129
267
139
75°F
289
121
301
128
292
136
310
146
85°F
331
124
348
131
334
140
355
151
95°F
374
126
393
134
379
142
400
154
105°F
425
130
450
138
430
145
456
158
115°F
481
133
507
141
484
148
514
161
TABLE 12
240 Reheat Compressor 1 Frequency 62Hz - 581021-01
Outdoor
Coil En
tering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Dis
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc.
+5
psig
65°F
263
122
296
126
239
126
273
140
75°F
304
126
336
126
276
133
312
144
85°F
348
129
384
128
318
138
357
148
95°F
387
129
405
129
373
140
389
148
105°F
442
133
464
133
424
144
440
151
115°F
500
137
523
136
477
147
497
152
TABLE 13
300 Std. Compressor 1 Frequency 68Hz - 581022-01
Outdoor
Coil En
tering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Dis
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc.
+5
psig
65°F
260
115
260
118
272
117
269
119
75°F
301
118
304
124
316
126
314
130
85°F
345
121
350
127
362
133
360
138
95°F
387
126
407
130
403
138
412
145
105°F
437
128
460
134
455
141
466
149
115°F
490
131
519
137
510
144
522
154
TABLE 14
300 Reheat Compressor 1 Frequency 68Hz - 581023-01
Outdoor
Coil En
tering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Dis
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc.
+5
psig
65°F
274
121
295
120
259
114
275
120
75°F
316
124
339
122
301
123
317
128
85°F
363
126
387
124
346
131
362
135
95°F
415
129
442
127
395
137
414
141
105°F
469
132
497
130
447
142
464
144
115°F
525
136
558
133
502
145
519
147
E-Charge Verification - Approach Method - AHRI
Testing (Fin/Tube Coil)
1- Using the same thermometer, compare liquid
temperature to outdoor ambient temperature.
Approach Temperature = Liquid temperature (at
condenser outlet) minus ambient temperature.
2- Approach temperature should match values in table
15. An approach temperature greater than value
shown indicates an undercharge. An approach
temperature less than value shown indicates an
overcharge.
3- The approach method is not valid for grossly over or
undercharged systems.
Use tables
as a
guide for typical operating pressures.
TABLE 15
APPROACH TEMPERATURES - FIN/TUBE COIL
Unit
Liquid Temp. Minus Ambient Temp.
1st Stage
2nd Stage
3rd Stage
4th Stage
156 Std.
3.0°F + 1
(1.7°C +0.5)
6.0°F + 1
(3.3°C +0.5)
6.5°F + 1
(3.6°C +0.5)
NA
156
Reheat
1.7°F+1
(0.9°C+0.5)
1.7°F+1
(0.9°C+0.5)
2.7°F+1
(1.5°C+0.5)
NA
180 Std.
2.5°F + 1
(1.4°C +0.5)
5.0°F + 1
(2.8°C +0.5)
5.5°F + 1
(3.1°C +0.5)
NA
180
Reheat
1.0°F + 1
(0.6°C +0.5)
2.8°F + 1
(1.6°C +0.5)
4.8°F + 1
(2.7°C +0.5)
NA
210 Std.
1.0°F + 1
(0.6°C +0.5)
5.5°F + 1
(3.1°C +0.5)
3.0°F + 1
(1.7°C +0.5)
6.0°F + 1
(3.3°C +0.5)
210
Reheat
2.5°F + 1
(1.4°C +0.5)
3.7°F + 1
(2.1°C +0.5)
6.0°F + 1
(3.3°C +0.5)
4.3°F + 1
(2.4°C +0.5)
240 Std.
3.5°F + 1
(1.9°C +0.5)
8.3°F + 1
(4.6°C +0.5)
4.7°F + 1
(2.6°C +0.5)
7.5°F + 1
(4.2°C +0.5)
240
Reheat
1.9°F + 1
(1.1°C +0.5)
3.8°F + 1
(2.1°C +0.5)
2.2°F + 1
(1.2°C +0.5)
5.4°F + 1
(3.0°C +0.5)
300 Std.
1.5°F+1
(0.8°C+0.5)
5.5°F+1
(3.1°C+0.5)
4.0°F+1
(2.2°C+0.5)
6.5°F+1
(3.6°C+0.5)
300
Reheat
2.8°F+1
(1.5°C+0.5)
4.2°F+1
(2.3°C+0.5)
3.8°F+1
(2.1°C+0.5)
5.4°F+1
(3.0°C+0.5)