Page 38
LGM/LCM156, 180, 210, 240, 300
TABLE 21
REHEAT OPERATION
Thermostat Mode With 24V Humidistat
Humidity Demands
Operation
24V Demand for Dehumidification only
Compressor 1 reheat on
Compressor 1 operates at 100%
Reheat valve is energized
Remaining compressors are off
Blower and outdoor fans modulate to maintain indoor coil and
discharge air temperatures
24V Demand for Dehumidification only is still
present after Five Minutes
Compressor 1 & 2 reheat on
Compressor 1 operates at 100%
Reheat valves are energized
Remaining compressor(s) is/are off
Blower and outdoor fans modulate to maintain indoor coil and dis
charge air temperatures
Thermostat Mode with Zone Relative Humidity (RH) Sensor
Zone humidity is greater than Se2%
Compressor 1 reheat on
Compressor 1 modulates to maintain zone RH
Reheat valve is energized
Remaining compressors are off
Blower and outdoor fans modulate to maintain indoor coil and
discharge air temperatures
Zone humidity is greater than Se2%
OR
Zone humidity is greater than Setpoint for 5
minutes
Compressor 1 & 2 reheat on
Compressor 1 modulates to maintain zone RH
Reheat valves are energized
Remaining compressor(s) is/are off
Blower and outdoor fans modulate to maintain indoor coil and
discharge air temperatures