Page 1
7
BLOWER DATA
FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS
Motor Efficiency
Nominal
hp
Maximum
hp
Drive Kit Number
RPM Range
Standard or High
2
2.30
1
535 - 725
Standard or High
2
2.30
2
710 - 965
Standard
3
3.45
1
535 - 725
Standard
3
3.45
2
710 - 965
High
3
3.45
3
685 - 856
High
3
3.45
4
850 - 1045
Standard
5
5.75
3
685 - 856
Standard
5
5.75
4
850 - 1045
Standard
5
5.75
5
945 - 1185
Standard
7.5
8.63
6
850 - 1045
Standard
7.5
8.63
7
945 - 1185
Standard
7.5
8.63
8
1045 - 1285
Standard
10
11.50
7
945 - 1185
Standard
10
11.50
10
1045 - 1285
Standard
10
11.50
11
1135 - 1365
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable
output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
NOTE – Units equipped with Multi-Stage Air Volume option are limited to a motor service factor of 1.0.
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE
Air
Volume
cfm
Wet Indoor Coil
Condenser
Reheat
Coil
Gas Heat Exchanger
Electric
Heat
Econo-
mizer
Filters
Horizontal
Roof Curb
156,
180
210,
240,
300
Low/
Standard
Heat
Medium
Heat
High
Heat
156U
thru
240U
300U
in. w.g.
in.
w.g.
in. w.g.
in. w.g.
in. w.g. in. w.g. in. w.g. in. w.g. MERV 8 MERV 13 in. w.g. in. w.g.
2750
.01
.02
.01
.02
.04
.05
- - -
- - -
.01
.03
.03
-
3000
.01
.02
.01
.03
.04
.05
- - -
- - -
.01
.03
.04
-
3250
.01
.03
.01
.03
.05
.06
- - -
- - -
.01
.04
.04
.01
3500
.01
.03
.02
.03
.05
.06
- - -
- - -
.01
.04
.05
.01
3750
.01
.03
.02
.04
.06
.07
- - -
- - -
.01
.04
.05
.01
4000
.02
.04
.02
.04
.06
.07
- - -
- - -
.01
.04
.06
.02
4250
.02
.04
.02
.04
.06
.08
- - -
- - -
.01
.05
.07
.02
4500
.02
.05
.02
.05
.07
.09
- - -
- - -
.01
.05
.07
.02
4750
.02
.05
.02
.05
.08
.10
- - -
- - -
.02
.05
.08
.03
5000
.02
.05
.02
.05
.09
.11
- - -
- - -
.02
.06
.08
.03
5250
.02
.06
.03
.06
.10
.12
- - -
- - -
.02
.06
.09
.04
5500
.02
.07
.03
.06
.10
.13
- - -
- - -
.02
.06
.10
.04
5750
.03
.07
.03
.06
.11
.14
- - -
- - -
.02
.07
.11
.05
6000
.03
.08
.03
.07
.12
.15
.01
- - -
.03
.07
.11
.06
6250
.03
.08
.03
.07
.12
.16
.01
.01
.03
.07
.12
.07
6500
.03
.09
.04
.08
.13
.17
.01
.02
.03
.08
.13
.08
6750
.04
.10
.04
.08
.14
.18
.01
.03
.03
.08
.14
.08
7000
.04
.10
.04
.09
.15
.19
.01
.04
.04
.08
.15
.09
7250
.04
.11
.04
.09
.16
.20
.01
.05
.04
.09
.16
.10
7500
.05
.12
.05
.10
.17
.21
.01
.06
.04
.09
.17
.11
8000
.05
.13
.05
.11
.19
.24
.02
.09
.05
.10
.19
.13
8500
.06
.15
.05
.12
.20
.26
.02
.11
.05
.10
.21
.15
9000
.07
.16
.06
.13
.23
.29
.04
.14
.06
.11
.24
.17
9500
.08
.18
.07
.14
.25
.32
.05
.16
.07
.12
.26
.19
10,000
.08
.20
.07
.16
.27
.35
.06
.19
.07
.12
.29
.21
10,500
.09
.22
.08
.17
.30
.38
.09
.22
.08
.13
.31
.24
11,000
.11
.24
.08
.18
.31
.40
.11
.25
.09
.14
.34
.27