D-Refrigerant Charge and Check - Fin/Tube Coil
WARNING-Do not exceed nameplate charge under any condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,
reclaim the charge,
evacuate the system and
add
required nameplate charge.
NOTE - System charging is not recommended below
60°F (15°C). In temperatures below 60°F (15°C),
the
charge
must
be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in normal cooling mode.
1- Attach gauge manifolds to discharge and suction
lines. With the economizer disabled, operate the unit
in
cooling mode at high speed
using the following
mobile service app menu path:
SERVICE>TEST>COOL>COOL 4
2- Use a thermometer to accurately measure the
outdoor ambient temperature.
3- Apply the outdoor temperature to tables 5 through 14
to determine normal operating pressures.
Pressures
are listed for sea level applications at 80
°
F dry bulb
and 67
°
F wet bulb return air.
4- Compare the normal operating pressures to the
pressures obtained from the gauges. Minor
variations in these pressures may be expected due to
differences in installations. Significant differences
could mean that the system is not properly charged
or that a problem exists with some component in the
system.
Correct any system problems before
proceeding.
5- If discharge pressure is high, remove refrigerant from
the system. If discharge pressure is low, add
refrigerant to the system.
Add or remove charge in increments.
Allow the system to stabilize each time
refrigerant is added or removed.
6- Use the following approach method along with the
normal operating pressures to confirm readings.
TABLE 5
156 Std. Compressor 1 Frequency 56Hz - 581014-01
Outdoor
Coil En
tering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
65°F
228
127
256
131
258
140
75°F
267
130
295
134
298
148
85°F
309
133
337
136
340
153
95°F
352
135
383
139
387
156
105°F
403
139
432
142
433
159
115°F
457
142
485
145
486
162
TABLE 6
156 Reheat Compressor 1 Frequency 56Hz - 581015-01
Outdoor
Coil
Entering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Disch.
+10
psig
Suct.
+5
psig
Disch.
+10
psig
Suct.
+5
psig
Disch.
+10
psig
Suct.
+5
psig
65°F
230
123
274
127
260
140
75°F
267
126
313
129
299
144
85°F
309
129
353
132
341
147
95°F
355
133
398
135
385
150
105°F
404
135
447
137
432
153
115°F
463
139
507
140
485
156
TABLE 7
180 Std. Compressor 1 Frequency 56Hz - 581016-01
Outdoor
Coil
Entering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Disch.
+10
psig
Suct.
+5
psig
Disch.
+10
psig
Suct.
+5
psig
Disch.
+10
psig
Suct.
+5
psig
65°F
232
123
276
131
279
141
75°F
267
129
313
133
315
147
85°F
311
132
360
136
362
151
95°F
357
135
406
138
408
154
105°F
403
137
456
141
455
158
115°F
456
140
511
144
510
161
TABLE 8
180 Reheat Compressor 1 Frequency 56Hz - 581017-01
Outdoor
Coil
Entering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Disch.
+10
psig
Suct.
+5
psig
Disch.
+10
psig
Suct.
+5
psig
Disch.
+10
psig
Suct.
+5
psig
65°F
233
122
291
129
267
132
75°F
270
127
330
131
307
138
85°F
313
129
373
133
348
143
95°F
360
134
430
137
398
147
105°F
411
136
472
139
441
149
115°F
469
139
531
142
495
152
TABLE 9
210 Std. Compressor 1 Frequency 48Hz - 581018-01
Outdoor
Coil En
tering
Air
Temp
Circuit 1
Circuit 2
Circuit 3
Circuit 4
Dis
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc
+5
psig
Dis.
+10
psig
Suc.
+5
psig
65°F
245
125
255
127
253
139
259
140
75°F
283
127
294
130
290
143
299
146
85°F
323
129
336
133
330
146
343
149
95°F
368
131
386
136
376
148
393
151
105°F
418
134
435
139
425
152
440
153
115°F
472
137
489
142
479
154
496
155