BLOWER DATA
SL280UH110V60C BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1690
1855
+18%
1605
1765
+12%
1525
1675
+6%
1445
1585
Factory Default
1360
1495
–6%
1280
1405
–12%
1200
1315
–18%
1115
1230
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low Medium-High
2
High
Low
Medium-Low Medium-High
2
High
+
1060
1220
1330
1565
1535
1710
1910
2210
Factory Default
970
1075
1180
1430
1400
1565
1715
2015
–
875
980
1070
1255
1260
1400
1560
1815
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28% and 38% of the selected second stage cooling speed - minimum 450 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.
SL280UH110V60C BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
Motor Watts @ Various External Static Pressures - in. wg.
First Stage
Second Stage
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
+ Setting
Cooling
Speed
Low
89 116 144 159
201 222
245 274 298 234 259 304 360 385 408 451 484 530 553 596
Med-Low
108
135 170 196
228
259 286 320 343 297 340 380 409 459 502 539 570 616 660 702
Med-High 136 164
202
236 269 300 331 370 392 390 420 497 530 585 630 677 727 777 815 854
High
252 275 329 366 396 441 472 493 537 702 734 780 841 907 957 1013 1048
1100
1124 1148
Factory Default
Cooling
Speed
Low
71
98
118
139 166 184 207 237 262 179 203 244
281
329 356 388 425 453 480 519
Med-Low 86
118
138 154 187
212
237 266 291 223 251
288
342 377 399 449 474 513 548 578
Med-High 99 132 160 184
222
254 277 308 343 299 341 384 420 472 497 540 599 632 674 709
High
192 227 258 299 333 376 409 434 471 493 540 591 653 705 760 829 869 919 965 1005
– Setting
Cooling
Speed
Low
60
78 104
122
144 168 187 205 226 133 162 191 225 262 289 324 357 385 410 436
Med-Low 68
94 116 132 150 177 203
220
251 163 189 224 263 292 333 364 392 431 458 473
Med-High
80
109
128
151 174 204 229 252 279 224 251 293 326 370 398 439 467 491 531 570
High