Page 73
XP17
TO VAPOR
SERVICE VALVE
HFC-410A
MANIFOLD GAUGE SET
OUTDOOR UNIT
HIGH
LOW
NITROGEN
NOTE — Normally, the high pressure hose is connected to the liquid line port.
However, connecting it to the vapor port better protects the manifold gauge set
from high pressure damage.
A
With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set.
Open the valve on the HFC-410A cylinder (vapor only).
B
Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in a trace amount of
HFC-410A.
[A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure].
Close the valve
on the HFC-410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
C
Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D
Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the
line set and the indoor unit.
E
After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable
with a leak detector
.
F
After leak testing disconnect gauges from service ports.
LINE SET AND INDOOR COIL
After the line set has been connected to the indoor and outdoor units, check the line set connections and
indoor unit for leaks. Use the following procedure to test for leaks:
LEAK TEST
A
Connect an HFC-410A manifold gauge set high
pressure hose to the vapor valve service port.
B
With both manifold valves closed, connect the
cylinder of HFC-410A refrigerant to the center port
of the manifold gauge set.
1
CONNECT GAUGE SET
2
TEST FOR LEAKS
A
B
NOTE — Later in the procedure, the HFC-410A
container will be replaced by the nitrogen container.
Summary of Contents for iComfort SL18XC1 Series
Page 44: ...Page 44 XP17 Figure 21 Typical XP17 Wiring XP17 XX 230 06...
Page 45: ...Page 45 XP17 Factory Wiring Diagrams Figure 22 Typical Factory Wiring XP17 XX 230 01...
Page 46: ...Page 46 XP17 Figure 23 Typical Factory Wiring XP17 XX 230 02...
Page 47: ...Page 47 XP17 Figure 24 Typical Factory Wiring XP17 XX 230 03 and 05...
Page 48: ...Page 48 XP17 Figure 25 Typical Factory Wiring XP17 XX 230 06...