Page 50
XP17
XC21 iComfort™ Outdoor Unit
Wiring Detail with Utility Load Shedding - Preferred and Only Wiring Method
0
Field-Provided Relay -
Part Number 69J79
(silver-gold diffused
contacts)
Utility Load Control Receiver
Contacts (N.C. contacts shown,
verify contact configuration)
5
2
A
B
7
(c)
(NO)
(NC)
Outdoor Control Part Number
103369-03
Figure 27. Preferred Method - Outdoor Control - 103369-03
NON- PREFERRED WIRING (OUTDOOR CONTROLS -
103369-01 AND 103369-02 ONLY)
1.
Utility Load Shedding Mode ACTIVATED (Utility
Cycled Unit OFF)
– The normally closed set of
contacts in the utility load control receiver
open
. This
interrupts the 24VAC signal from the
Y1 Out
terminal
on the outdoor control to the compressor contactor coil
and the compressor will be cycled
OFF
. The outdoor
fan will continue to operate during a thermostat
demand. The 7‐segment display on the outdoor
control will
NOT
display an alert code and the iComfort
WiFi
®
thermostat will
NOT
display an alert. The
customer will not be notified by email when the load
shedding mode is activated by the utility company.
Note
Some utilities may require the entire outdoor
unit to cycle off during utility load shedding. If the entire
outdoor unit is required to cycle off, the "preferred
wiring method" shown in figure 27 must be used.
2.
Utility Load Shedding Mode DEACTIVATED
(Normal Equipment Operation)
– When load
shedding is not required, the contacts in the utility load
control receiver are closed. The circuit is completed
between the
Y1 Out
terminal on the outdoor control to
the compressor contactor coil. The outdoor unit will
return to normal operation.
Summary of Contents for iComfort SL18XC1 Series
Page 44: ...Page 44 XP17 Figure 21 Typical XP17 Wiring XP17 XX 230 06...
Page 45: ...Page 45 XP17 Factory Wiring Diagrams Figure 22 Typical Factory Wiring XP17 XX 230 01...
Page 46: ...Page 46 XP17 Figure 23 Typical Factory Wiring XP17 XX 230 02...
Page 47: ...Page 47 XP17 Figure 24 Typical Factory Wiring XP17 XX 230 03 and 05...
Page 48: ...Page 48 XP17 Figure 25 Typical Factory Wiring XP17 XX 230 06...