background image

Page 14

VI − MAINTENANCE

In order to maintain the warranty on this equipment, the
XP13 system must be serviced annually and a record of
service maintained. The following should be checked be-
tween annual maintenance:

A − Outdoor Unit

 1 − Clean and inspect the outdoor coil. The coil may be

flushed with a water hose. Ensure the power is turned
off before you clean the coil.

 2 − Condenser fan motor is prelubricated and sealed. No

further lubrication is needed.

 3 − Visually inspect connecting lines and coils for evidence

of oil leaks.

 4 − Check wiring for loose connections.

 5 − Check for correct voltage at unit (unit operating).

 6 − Check amp−draw condenser fan motor.

Unit nameplate _________ Actual ____________ .

NOTE − If owner complains of insufficient cooling, the unit
should be gauged and refrigerant charge checked. Refer
to section on refrigerant charging in this instruction.

 1 − Clean and inspect condenser coil. (Coil may be flushed

with a water hose after disconnecting power).

 2 − Visually inspect all connecting lines, joints and coils for

evidence of oil leaks.

B − Indoor Coil

 1 − Clean coil, if necessary.

 2 − Check  connecting  lines  and  coils  for  evidence  of  oil

leaks.

 3 − Check the condensate line and clean it if necessary.

C − Indoor Unit

 1 − Clean or change filters.

 2 − Adjust blower speed for cooling. Measure the pressure

drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.

 3 −

Belt Drive Blowers − 

Check belt for wear and proper ten-

sion.

 4 − Check all wiring for loose connections

 5 − Check for correct voltage at unit (blower operating).

 6 − Check amp−draw on blower motor

Unit nameplate_________ Actual ____________.

VII − BRAZING

Before brazing remove access panels and any piping pan-
els to avoid burning off paint. Be aware of any components
ie, service valves, reversing valve, pressure switches that
may be damaged due to brazing heat.
When making line set connections, use 1 to 2 psig dry nitro-
gen to purge the refrigerant piping. This will help to prevent
oxidation into the system.

WARNING

Danger of explosion: Can cause equipment damage,
injury or death. When using a high pressure gas such
as dry nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that can control
the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).

 1 − .Cut ends of copper square (free from nicks or dents).

Debur the ends. The pipe must remain round, do not
pinch end of line.

 2 − Wrap wet rag around any components that may be da-

maged.

 3 − Use silver alloy brazing rods (5 or 6 percent minimum

silver alloy for copper to copper brazing or 45 percent
silver alloy for copper to brass or copper to steel braz-
ing) which are rated for use with R−22 and R−410A re-
frigerant.

 4 − After brazing quench the joints with a wet rag to prevent

possible heat damage to any components.

Summary of Contents for Elite XP13018

Page 1: ...RNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning or installation and opera ti...

Page 2: ...230V 208 230V 208 230V 3 Maximum overcurrent protection amps 20 30 30 35 35 40 50 60 2 Minimum circuit ampacity 11 9 17 5 18 4 21 6 21 9 23 2 28 9 34 6 Compressor Rated load amps 8 97 13 46 14 1 16 6...

Page 3: ...1 OUTDOOR FAN COMPRESSOR HIGH PRESSURE SWITCH REVERSING VALVE FILTER DRIER CONTROL BOX EXPANSION VALVE VAPOR LINE SERVICE VALVE LIQUID LINE SERVICE VALVE A Control Box Figure 2 XP13 units are not equi...

Page 4: ...the TEST position at power up the control will ignore the test pins When the jumper is placed across the TEST pins for two seconds the control will enter the defrost mode If the jumper is removed befo...

Page 5: ...TION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls f...

Page 6: ...oving the four screws securing the fan assembly See figure9 The grill fan assembly can be removed from the cabinet as one piece See figure 10 The condenser fan motor is removed from the fan guard by r...

Page 7: ...pole single throw high pressure switch is located in the liquid line This switch shuts off the compres sor when liquid line pressure rises above the factory setting The switch is normally closed and i...

Page 8: ...ON OF REFRIGERANT FLOW SERVICE PORT SUCTION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD INTERNAL COMPRESSOR LIMIT DISTRIBUTOR INDOOR COIL COIL SENSOR FIGURE...

Page 9: ...ation and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is complete replace service por...

Page 10: ...only 3 Open the high pressure side of the manifold to allow the R 410A into the line set and indoor unit Weigh in a trace amount of R 410A A trace amount is a maximum of 2 ounces 57 g or 3 pounds 31 k...

Page 11: ...urn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off th...

Page 12: ...5 Charge Using the Approach Method Outdoor Temperature 65 F 18 C The following procedure is intended as a general guide and is for use on expansion valve systems only For best results indoor temperatu...

Page 13: ...0A refriger ant absorb moisture very quickly It is very impor tant that the refrigerant system be kept closed as much as possible DO NOT remove line set caps or service valve stub caps until you are r...

Page 14: ...the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure 3 Belt Drive Blowers Check belt for wear and proper ten sion 4 Check a...

Page 15: ...Page 15 VIII WIRING DIAGRAM AND SEQUENCE OF OPERATION 5 6 1 2 4 3 3 6...

Page 16: ...tdoor fan motor B4 are de energized and stop immediately Terminal O is de energized when indoor room thermo stat is out of cooling mode de energizing the reversing valve L1 Heating demand initiates at...

Reviews: