background image

Page 10

The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak−free
seal.

Ball Valve (Valve Open)

Schrader valve

service port

service port

cap

stem cap

stem

Use Adjustable Wrench

To open:  rotate Stem Clockwise 90°.

To close:  rotate Stem Counter-clockwise 90°.

ball

(shown open)

to outdoor coil

to indoor coil

FIGURE 14

IV − CHARGING

A − Leak Testing

After the line set has been connected to the indoor and out-
door units, check the line set connections and indoor unit
for leaks.

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.

Failure to follow this warning may result in personal
injury or death.

WARNING

Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause damage by fire
and / or an explosion, that can re-
sult in personal injury or death.

WARNING

Danger of explosion!
When using a high pressure gas such
as dry nitrogen to pressurize a refriger-
ant or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).

Using an Electronic Leak Detector or Halide

 1 − Connect a cylinder of R−410A to the center port of the

manifold gauge set.

 2 − With both manifold valves closed, open the valve on the

R−410A cylinder (vapor only).

 3 − Open the high pressure side of the manifold to allow the

R−410A into the line set and indoor unit. Weigh in a
trace amount of R−410A.

 

[A trace amount is a maximum

of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.]
Close the valve on the R−410A cylinder and the valve
on the high pressure side of the manifold gauge set.
Disconnect the R−410A cylinder.

 4 − Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

 5 − Connect the manifold gauge set high pressure hose to

the vapor valve service port. 

(Normally, the high pres-

sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage.)

 6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).

Open the valve on the high side of the manifold gauge
set which will pressurize line set and indoor unit.

 7 − After a few minutes, open a refrigerant port to ensure

the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and R−410A
mixture. Correct any leaks and recheck.

B − Evacuating the System

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.

NOTE − This evacuation process is adequate for a new
installation with clean and dry lines. If excessive mois-
ture is present, the evacuation process may be re-
quired more than once.

Summary of Contents for Elite XP13018

Page 1: ...RNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning or installation and opera ti...

Page 2: ...230V 208 230V 208 230V 3 Maximum overcurrent protection amps 20 30 30 35 35 40 50 60 2 Minimum circuit ampacity 11 9 17 5 18 4 21 6 21 9 23 2 28 9 34 6 Compressor Rated load amps 8 97 13 46 14 1 16 6...

Page 3: ...1 OUTDOOR FAN COMPRESSOR HIGH PRESSURE SWITCH REVERSING VALVE FILTER DRIER CONTROL BOX EXPANSION VALVE VAPOR LINE SERVICE VALVE LIQUID LINE SERVICE VALVE A Control Box Figure 2 XP13 units are not equi...

Page 4: ...the TEST position at power up the control will ignore the test pins When the jumper is placed across the TEST pins for two seconds the control will enter the defrost mode If the jumper is removed befo...

Page 5: ...TION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls f...

Page 6: ...oving the four screws securing the fan assembly See figure9 The grill fan assembly can be removed from the cabinet as one piece See figure 10 The condenser fan motor is removed from the fan guard by r...

Page 7: ...pole single throw high pressure switch is located in the liquid line This switch shuts off the compres sor when liquid line pressure rises above the factory setting The switch is normally closed and i...

Page 8: ...ON OF REFRIGERANT FLOW SERVICE PORT SUCTION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD INTERNAL COMPRESSOR LIMIT DISTRIBUTOR INDOOR COIL COIL SENSOR FIGURE...

Page 9: ...ation and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is complete replace service por...

Page 10: ...only 3 Open the high pressure side of the manifold to allow the R 410A into the line set and indoor unit Weigh in a trace amount of R 410A A trace amount is a maximum of 2 ounces 57 g or 3 pounds 31 k...

Page 11: ...urn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off th...

Page 12: ...5 Charge Using the Approach Method Outdoor Temperature 65 F 18 C The following procedure is intended as a general guide and is for use on expansion valve systems only For best results indoor temperatu...

Page 13: ...0A refriger ant absorb moisture very quickly It is very impor tant that the refrigerant system be kept closed as much as possible DO NOT remove line set caps or service valve stub caps until you are r...

Page 14: ...the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure 3 Belt Drive Blowers Check belt for wear and proper ten sion 4 Check a...

Page 15: ...Page 15 VIII WIRING DIAGRAM AND SEQUENCE OF OPERATION 5 6 1 2 4 3 3 6...

Page 16: ...tdoor fan motor B4 are de energized and stop immediately Terminal O is de energized when indoor room thermo stat is out of cooling mode de energizing the reversing valve L1 Heating demand initiates at...

Reviews: