background image

Page 4

2 − Dual Capacitor C12

The compressor and fan in XP13 series units use permanent
split capacitor motors. The capacitor is located inside the unit
control box (see figure 2). A single dual" capacitor (C12) is
used for both the fan motor and the compressor (see unit wir-
ing diagram). The fan side and the compressor side of the ca-
pacitor have different MFD ratings. See side of capacitor for
ratings.

3 − Defrost Control

The XP13 defrost system includes two components: a de-
frost thermostat and a defrost control.

Defrost Thermostat (Defrost Switch S6)

The defrost thermostat is located on the liquid line between
the check/expansion valve and the distributor. When de-
frost thermostat senses 42°F (5.5°C) or cooler, the thermo-
stat contacts close and send a signal to the defrost control
board to start the defrost timing. It also terminates defrost
when the liquid line warms up to 70°F (21°C).

Defrost Control

The defrost control board includes the combined functions
of a time/temperature defrost control, defrost relay, diag-
nostic LEDs and terminal strip for field wiring connections.
The control provides automatic switching from normal heat-
ing operation to defrost mode and back. During compressor
cycle (call for defrost), the control accumulates compressor
run times at 30-, 60-, or 90-minute field−adjustable inter-
vals. If the defrost thermostat is closed when the selected
compressor run time interval ends, the defrost relay is ener-
gized and defrost begins.

XP13 Outdoor Unit Defrost Control Board

24V TERMINAL
STRIP
CONNECTIONS

DIAGNOSTIC
LEDS

HIGH PRESSURE

SWITCH

TEST

PINS

FIELD SELECT

TIMING PINS

REVERSING

VALVE

DEFROST

THERMOSTAT

LOW PRESSURE

SWITCH

COMPRESSOR

DELAY PINS

S4

S87

FIGURE 4

Defrost Control Timing Pins

Each timing pin selection provides a different accumu-
lated compressor run time period for one defrost cycle.
This time period must occur before a defrost cycle is initi-
ated. The defrost interval can be adjusted to 30, 60 or 90
minutes (see figure 4). The defrost timing jumper is facto-

ry−installed to provide a 60−minute defrost interval. If the
timing selector jumper is not in place, the control defaults
to a 90−minute defrost interval. The maximum defrost pe-
riod is 14 minutes and cannot be adjusted.
A TEST option is provided for troubleshooting. 

The TEST

mode may be started any time the unit is in the heating
mode and the defrost thermostat is closed or jump-
ered. 

If the jumper is in the TEST position at power-up, the

control will ignore the test pins. When the jumper is placed
across the TEST pins for two seconds, the control will enter
the defrost mode. If the jumper is removed before an addi-
tional 5−second period has elapsed (7 seconds total), the
unit will remain in defrost mode until the defrost thermostat
opens or 14 minutes have passed. If the jumper is not re-
moved until after the additional 5−second period has
elapsed, the defrost will terminate and the test option will
not function again until the jumper is removed and re−ap-
plied.

Compressor Delay

The defrost board has a field−selectable function to reduce
occasional sounds that may occur while the unit is cycling in
and out of the defrost mode. The compressor will be cycled
off for 30 seconds going in and out of the defrost mode
when the compressor delay jumper is removed.

NOTE − The 30-second compressor feature is ignored
when the defrost test pins are jumpered.

Time Delay

The timed-off delay is five minutes long. The delay helps to
protect the compressor from short-cycling in case the pow-
er to the unit is interrupted or a pressure switch opens. The
delay is bypassed by placing the timer select jumper across
the TEST pins for 0.5 seconds.

Pressure Switch Circuit

The defrost control incorporates two pressure switch cir-
cuits. The high pressure switch (S4) is factory-connected to
the board’s HI PS terminals (see figure 4). The board also
includes a low pressure, or loss-of-charge-pressure, switch
(S87). Switches are shown in the unit  wiring diagram. Dur-
ing a single demand cycle, the defrost control will lock out
the unit after the fifth time that the circuit is interrupted by
any pressure switch wired to the control board. In addition,
the diagnostic LEDs will indicate a locked-out pressure
switch after the fifth occurrence of an open pressure switch
(see Table 1). The unit will remain locked out until power to
the board is interrupted, then re-established or until the
jumper is applied to the TEST pins for 0.5 seconds.
Some XP13 units will be equipped with an optional by−pass
switch wired in parallel with the low pressure switch (S87).
This by−pass switch prevents  nuisance trips when ambient
conditions drop below 15° F.

NOTE − The defrost control board ignores input from the
low-pressure switch terminals as follows:
during the TEST mode,
during the defrost cycle,
during the 90-second start-up period,
and for the first 90 seconds each time the reversing valve

switches heat/cool modes.

Diagnostic LEDs

The defrost board uses two LEDs for diagnostics. The LEDs
flash a specific sequence according to the condition.

Summary of Contents for Elite XP13018

Page 1: ...RNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning or installation and opera ti...

Page 2: ...230V 208 230V 208 230V 3 Maximum overcurrent protection amps 20 30 30 35 35 40 50 60 2 Minimum circuit ampacity 11 9 17 5 18 4 21 6 21 9 23 2 28 9 34 6 Compressor Rated load amps 8 97 13 46 14 1 16 6...

Page 3: ...1 OUTDOOR FAN COMPRESSOR HIGH PRESSURE SWITCH REVERSING VALVE FILTER DRIER CONTROL BOX EXPANSION VALVE VAPOR LINE SERVICE VALVE LIQUID LINE SERVICE VALVE A Control Box Figure 2 XP13 units are not equi...

Page 4: ...the TEST position at power up the control will ignore the test pins When the jumper is placed across the TEST pins for two seconds the control will enter the defrost mode If the jumper is removed befo...

Page 5: ...TION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls f...

Page 6: ...oving the four screws securing the fan assembly See figure9 The grill fan assembly can be removed from the cabinet as one piece See figure 10 The condenser fan motor is removed from the fan guard by r...

Page 7: ...pole single throw high pressure switch is located in the liquid line This switch shuts off the compres sor when liquid line pressure rises above the factory setting The switch is normally closed and i...

Page 8: ...ON OF REFRIGERANT FLOW SERVICE PORT SUCTION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD INTERNAL COMPRESSOR LIMIT DISTRIBUTOR INDOOR COIL COIL SENSOR FIGURE...

Page 9: ...ation and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is complete replace service por...

Page 10: ...only 3 Open the high pressure side of the manifold to allow the R 410A into the line set and indoor unit Weigh in a trace amount of R 410A A trace amount is a maximum of 2 ounces 57 g or 3 pounds 31 k...

Page 11: ...urn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off th...

Page 12: ...5 Charge Using the Approach Method Outdoor Temperature 65 F 18 C The following procedure is intended as a general guide and is for use on expansion valve systems only For best results indoor temperatu...

Page 13: ...0A refriger ant absorb moisture very quickly It is very impor tant that the refrigerant system be kept closed as much as possible DO NOT remove line set caps or service valve stub caps until you are r...

Page 14: ...the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure 3 Belt Drive Blowers Check belt for wear and proper ten sion 4 Check a...

Page 15: ...Page 15 VIII WIRING DIAGRAM AND SEQUENCE OF OPERATION 5 6 1 2 4 3 3 6...

Page 16: ...tdoor fan motor B4 are de energized and stop immediately Terminal O is de energized when indoor room thermo stat is out of cooling mode de energizing the reversing valve L1 Heating demand initiates at...

Reviews: