background image

Page 13

TABLE 7

XP13 Normal Operating Pressures

Model

−018

−024

−024−2

−030

−036

−037

−042

−048

−060

Values below are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary.

Temp ºF (ºC)*

Liquid Line Pressure / Vapor Line Pressure

Cooling Operation

65 (18)

228 / 140

232 / 139

240 / 139

245 / 135

251 / 134

237 / 126

239 / 135

244 / 139

248 / 129

75 (24)

265 / 142

268 / 142

277 / 142

284 / 137

292 / 138

276 / 135

277 / 136

283 / 141

289 / 131

85 (29)

311 / 144

317 / 144

319 / 142

328 / 140

339 / 140

320 / 139

321 / 139

318 / 143

336 / 132

95 (35)

350 / 147

366 / 146

362 / 143

377 / 144

392 / 143

370 / 143

379 / 142

369 / 145

385 / 133

105 (41)

402 / 149

412 / 148

419 / 146

429 / 145

443 / 145

423 / 146

423 / 144

420 / 148

440 / 136

115 (45)

458 / 152

464 / 152

474 / 153

486 / 147

508 / 149

486 / 148

484 / 147

484 / 150

500 / 140

Heating Operation

20 (−7)

278 / 67

267 / 55

285 / 61

278 / 55

285 / 57

316 / 57

309 / 60

277 / 59

305 / 59

30 (−1)

 294 / 81

283 / 72

300 / 75

294 / 72

295 / 77

331 / 73

325 / 74

291 / 73

317 / 72

40 (4.5)

 310 / 96

299 / 89

312 / 92

307 / 88

304 / 96

342 / 90

336 / 89

294 / 92

328 / 85

50 (10)

328 / 116

315 / 109

329 / 110

324 / 107

331 / 106

355 / 109

355 / 107

323 / 106

348 / 105

60 (16)

350 / 135

331 / 130

342 / 125

341 / 126

361 / 112

376 / 118

376 / 118

350 / 124

370 / 127

*Temperature of the air entering the outdoor coil.

V − SERVICE AND RECOVERY

WARNING

Polyol ester (POE) oils used with R−410A refriger-
ant absorb moisture very quickly. It is very impor-
tant that the refrigerant system be kept closed as
much as possible. DO NOT remove line set caps or
service valve stub caps until you are ready to make
connections.

IMPORTANT

Use recovery machine rated for R410 refrigerant.

If the XP13 system must be opened for any kind of service,
such as compressor or drier replacement, you must take
extra precautions to prevent moisture from entering the
system. The following steps will help to minimize the
amount of moisture that enters the system during recovery
of R−410A.
 1 − Use a regulator−equipped nitrogen cylinder to break

the system vacuum. Do not exceed 5 psi. The dry  nitro-
gen will fill the system, and will help purge any mois-
ture.

 2 − Remove the faulty component and quickly seal the sys-

tem (using tape or some other means) to prevent addi-
tional moisture from entering the system.

 3 − Do not remove the tape until you are ready to install

new component.  Quickly install the replacement com-
ponent.

 4 − Evacuate the system to remove any moisture and other

non−condensables.

The XP13 system MUST be checked for moisture any
time the sealed system is opened.

Any moisture not absorbed by the polyol ester oil can be re-
moved by triple evacuation. Moisture that has been ab-
sorbed by the compressor oil can be removed by replacing
the drier.

IMPORTANT

Evacuation of system only will not remove mois-
ture from oil. Drier must be replaced  to eliminate
moisture from POE oil.

Summary of Contents for Elite XP13018

Page 1: ...RNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning or installation and opera ti...

Page 2: ...230V 208 230V 208 230V 3 Maximum overcurrent protection amps 20 30 30 35 35 40 50 60 2 Minimum circuit ampacity 11 9 17 5 18 4 21 6 21 9 23 2 28 9 34 6 Compressor Rated load amps 8 97 13 46 14 1 16 6...

Page 3: ...1 OUTDOOR FAN COMPRESSOR HIGH PRESSURE SWITCH REVERSING VALVE FILTER DRIER CONTROL BOX EXPANSION VALVE VAPOR LINE SERVICE VALVE LIQUID LINE SERVICE VALVE A Control Box Figure 2 XP13 units are not equi...

Page 4: ...the TEST position at power up the control will ignore the test pins When the jumper is placed across the TEST pins for two seconds the control will enter the defrost mode If the jumper is removed befo...

Page 5: ...TION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls f...

Page 6: ...oving the four screws securing the fan assembly See figure9 The grill fan assembly can be removed from the cabinet as one piece See figure 10 The condenser fan motor is removed from the fan guard by r...

Page 7: ...pole single throw high pressure switch is located in the liquid line This switch shuts off the compres sor when liquid line pressure rises above the factory setting The switch is normally closed and i...

Page 8: ...ON OF REFRIGERANT FLOW SERVICE PORT SUCTION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD INTERNAL COMPRESSOR LIMIT DISTRIBUTOR INDOOR COIL COIL SENSOR FIGURE...

Page 9: ...ation and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is complete replace service por...

Page 10: ...only 3 Open the high pressure side of the manifold to allow the R 410A into the line set and indoor unit Weigh in a trace amount of R 410A A trace amount is a maximum of 2 ounces 57 g or 3 pounds 31 k...

Page 11: ...urn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off th...

Page 12: ...5 Charge Using the Approach Method Outdoor Temperature 65 F 18 C The following procedure is intended as a general guide and is for use on expansion valve systems only For best results indoor temperatu...

Page 13: ...0A refriger ant absorb moisture very quickly It is very impor tant that the refrigerant system be kept closed as much as possible DO NOT remove line set caps or service valve stub caps until you are r...

Page 14: ...the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure 3 Belt Drive Blowers Check belt for wear and proper ten sion 4 Check a...

Page 15: ...Page 15 VIII WIRING DIAGRAM AND SEQUENCE OF OPERATION 5 6 1 2 4 3 3 6...

Page 16: ...tdoor fan motor B4 are de energized and stop immediately Terminal O is de energized when indoor room thermo stat is out of cooling mode de energizing the reversing valve L1 Heating demand initiates at...

Reviews: