Page 5
SPECIFICATIONS
General
Data
Model No.
EL15XP1-042
EL15XP1-048
EL15XP1-060
Nominal Tonnage
3.5
4
5
1
Sound Rating Number
72
73
73
Connections
(sweat)
Liquid line (o.d.) - in.
3/8
3/8
3/8
Suction line (o.d.) - in.
7/8
7/8
1-1/8
2
Refrigerant
R-410A charge furnished
10 lbs. 11 oz.
10 lbs. 11 oz.
12 lbs. 5 oz.
Outdoor
Coil
Net face area - sq. ft. Outer coil
24.9
24.9
29.1
Inner coil
24.1
24.1
28.2
Tube diameter - in.
5/16
5/16
5/16
No. of rows
2
2
2
Fins per inch
22
22
22
Outdoor
Fan
Diameter - in.
22
22
22
No. of blades
4
4
4
Motor hp
1/4
1/4
1/4
Cfm
4347
4347
4550
Rpm
843
843
830
Watts
299
299
307
Shipping Data - lbs. 1 pkg.
285
285
308
ELECTRICAL DATA
Line voltage data - 60hz
208/230V-1ph
208/230V-1ph
208/230V-1ph
3
Maximum overcurrent protection (amps)
45
45
50
4
Minimum circuit ampacity
25.8
26.2
29.6
Compressor
Rated load amps
19.2
19.6
22.2
Locked rotor amps
123.9
130
127.9
Power factor
.96
.98
.99
Outdoor Fan Motor
Full load amps
1.8
1.8
1.8
Locked rotor amps
3.2
3.2
3.2
CONTROLS
iComfort
®
E30 Smart Wi-Fi Thermostat
15S63
•
•
•
Remote Outdoor Temperature Sensor
X2658
•
•
•
OPTIONAL ACCESSORIES - ORDER SEPARATELY
Compressor Hard Start
Kit
Copeland
10J42
•
•
LG
88M91
•
45F08
•
•
•
Freezestat
3/8 in. tubing
93G35
•
•
•
5/8 in. tubing
50A93
•
•
•
58M81
•
•
•
5
Low Ambient Kit
54M89
•
•
•
Mild Weather Kit
11B97
•
•
•
Monitor Kit - Service Light
76F53
•
•
•
Outdoor
Thermostat Kit
Thermostat
10Z23
•
•
•
Mounting Box
31461
•
•
•
Refrigerant Line Sets
L15-65-30 L15-65-40
L15-65-50
•
•
•
6
Snow Guard
39-1/2 X 35-5/8 in.
Y1033
•
•
•
NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270.
2
additional refrigerant charge required.
3
HACR type breaker or fuse.
4
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
5
Crankcase Heater and Freezestat are recommended with Low Ambient Kit.
6
Adds 11-1/2 inches (292 mm) to unit height.