Page 15

Installing Indoor Metering Device

A

Attach  the  vapor  line  sensing  bulb  in  the  proper

orientation as illustrated to the right using the clamp and

screws provided.

NOTE 

— Confirm proper thermal contact between vapor line

and expansion bulb before insulating the sensing bulb once

installed.

B

Connect the equalizer line from the expansion valve to

the equalizer vapor port on the vapor line. Finger tighten

the flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.

TWO PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

VAPOR

LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID LINE

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR

FURTHER DETAILS)

SENSING

LINE

EQUALIZER

LINE

EXPANSION

VALVE

TEFLON

®

RING

(Uncased Coil Shown)

Sensing  bulb  insulation  is  required  if

mounted external to the coil casing. sensing

bulb installation for bulb positioning.

STUB

END

TEFLON

®

RING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

DISTRIBUTOR

ASSEMBLY

A

Remove  the  field-provided  fitting  that  temporary

reconnected the liquid line to the indoor unit's distributor

assembly.

B

Install one  of  the  provided  Teflon

®

  rings  around  the

stubbed end of the expansion valve and lightly lubricate

the connector threads and expose surface of the Teflon

®

ring with refrigerant oil.

C

Attach the stubbed end of the expansion valve to the

liquid line  orifice  housing.  Finger  tighten  and  use  an

appropriately sized wrench to turn an additional 1/2 turn

clockwise as illustrated in the figure above, or 20 ft-lb.

D

Place the remaining Teflon

®

 washer around the other

end of the expansion valve. Lightly lubricate connector

threads and  expose  surface  of  the  Teflon

®

  ring  with

refrigerant oil.

E

Attach the liquid line assembly to the expansion valve.

Finger tighten and use an appropriately sized wrench to

turn an additional 1/2 turn clockwise as illustrated in the

figure above or 20 ft-lb.

ON  7/8”  AND  LARGER LINES,

MOUNT  SENSING  BULB  AT

EITHER THE 4 OR 8 O'CLOCK

POSITION. NEVER MOUNT ON

BOTTOM OF LINE.

12

ON LINES SMALLER THAN

7/8”,  MOUNT  SENSING

BULB AT EITHER THE 3 OR

9 O'CLOCK POSITION.

12

BULB

VAPOR LINE

VAPOR LINE

NOTE — NEVER MOUNT ON BOTTOM OF LINE.

BULB

BULB

BULB

VAPOR LINE

FLARE NUT

COPPER FLARE

SEAL BONNET

MALE BRASS EQUALIZER

LINE FITTING

FLARE SEAL CAP

OR

1

2

3

4

5

6

7

8

9

10

11 12

1/2 Turn

SENSING BULB INSTALLATION

EQUALIZER LINE INSTALLATION

1

2

3

4

5

6

7

8

9

10

11 12

1/8 Turn

A

Remove and discard either the flare seal cap or flare nut

with copper flare seal bonnet from the equalizer line port

on the vapor line as illustrated in the figure to the right.

B

Remove and discard either the flare seal cap or flare nut

with copper flare seal bonnet from the equalizer line port on

the vapor line as illustrated in the figure to the right.

INDOOR EXPANSION VALVE INSTALLATION

FIGURE 8. Installing Indoor Expansion Valve

This outdoor unit is designed for use in systems that use a 

check expansion valve metering device at the indoor coil.
See the Lennox EL15XP1 Product Specification bulletin 

for approved expansion valve kit match-ups. The expan

-

sion valve unit can be installed internal or external to the 

indoor coil. 

In applications where an uncased coil is being installed in 

a field-provided plenum, install the expansion valve in a 

manner that will provide access for field servicing of the 

expansion valve. Refer to below illustration for reference 

during installation of expansion valve unit.

Summary of Contents for EL15XP1 Series

Page 1: ...tion 2 Dimensions 3 Specifications 4 Typical Unit Parts Arrangement 6 Operating Gauge Set and Service Valves 6 Unit Placement 8 New or Replacement Line Set 9 Brazing Connections 11 Flushing Line Set a...

Page 2: ...may be A clearance of 24 in must be maintained between two units 48 in 1219 mm clearance required on top of unit Model Number Identification Nominal SEER Unit Type P Heat Pump Outdoor Unit Refrigeran...

Page 3: ...5 2 51 END VIEW TOP VIEW VAPOR LINE CONNECTION LIQUID LINE CONNECTION UNIT SUPPORT FEET 16 7 8 429 26 7 8 683 30 3 4 781 3 1 8 79 8 3 4 222 3 3 4 95 4 5 8 117 UNIT SUPPORT FEET EL15XP1 018 TO 036 BASE...

Page 4: ...8 72 2 Power factor 98 98 96 99 Outdoor Fan Motor Full load amps 1 0 1 0 1 0 1 0 Locked rotor amps 1 9 1 9 1 9 1 9 CONTROLS iComfort E30 Smart Wi Fi Thermostat 15S63 Remote Outdoor Temperature Sensor...

Page 5: ...23 9 130 127 9 Power factor 96 98 99 Outdoor Fan Motor Full load amps 1 8 1 8 1 8 Locked rotor amps 3 2 3 2 3 2 CONTROLS iComfort E30 Smart Wi Fi Thermostat 15S63 Remote Outdoor Temperature Sensor X26...

Page 6: ...stripping of the various caps used the appropriately sized wrench should be used and fitted snugly over the cap before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap...

Page 7: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Page 8: ...ent of unit in relation to a window see the provided illustration in figure 3 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so...

Page 9: ...be a Polyol ester oil The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet Recommend adding oil to system based on the amount of refrigerant charge in the sys...

Page 10: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Page 11: ...dous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns...

Page 12: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Page 13: ...tions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE...

Page 14: ...ISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Page 15: ...reads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wrench to turn an additional 1 2...

Page 16: ...gauge set Disconnect the HFC 410A cylinder C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set D Adjust dry nitrogen pressure to 150 psig...

Page 17: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Page 18: ...to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage control power 24...

Page 19: ...CY HEAT EMERGENCY HEAT RELAY OUTDOOR THERMOSTAT THERMOSTAT INDOOR UNIT OUTDOOR UNIT COMMON 1ST STAGE AUXILIARY HEAT INDOOR BLOWER COMPRESSOR COMMON 1ST STAGE AUXILIARY HEAT R E W O P V 4 2 R E W O P V...

Page 20: ...ressure switches Defrost Thermostat S6 The defrost thermostat is located on the liquid line be tween the check expansion valve and the distributor When defrost thermostat senses 42 F 5 5 C or cooler t...

Page 21: ...CONNECTIONS TEST PINS P1 Note Component locations vary by board manufacturer SENSOR CONNECTION COIL AND AMBIENT SENSORS P4 REVERSING VALVE O OUT DELAY PINS P5 LOW AMBIENT THERMOSTAT PINS P3 DEFROST T...

Page 22: ...of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the defrost mode Units are shipped with jumper installed on DELAY...

Page 23: ...ature probe is de signed with a spring clip to allow mounting to the outside coil tubing The location of the coil sensor is important for proper defrost operation NOTE The demand defrost control accur...

Page 24: ...tem Remove any blockages or restrictions from coils and or fans Check indoor and outdoor fan motor for proper current draws Check system charge using subcooling method Check system operating pressures...

Page 25: ...e outdoor unit s coil should be performed by a trained service technician Contact your dealer and set up a schedule preferably twice a year but at least once a year to inspect and service your outdoor...

Page 26: ...ur dealer show you the location of the drain line and how to check for obstructions This would also apply to an auxiliary drain if installed Thermostat Operation See the thermostat homeowner manual fo...

Page 27: ...Page 27 Wiring and Sequence of Operation FIGURE 13 Typical Unit Wiring...

Page 28: ...Page 28 FIGURE 14 Typical Factory Wiring...

Page 29: ...emand cycle If the coil sensor temperature is still below the selected termination temperature the control will continue the defrost cycle until the cycle is terminated in one of the methods mentioned...

Page 30: ...um Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure Vapor P...

Reviews: