IOM BASIC CLIMATIC CONTROLLER - Page 17
parameters lists
Settings
Access
Ref.
Alarm Parameters
Unit Min Max Factory
General Password
Factory
Adjust.
Hidden
A01 L/P switch bypass time after compressor on
s
0
255
120
-
X
A02 Low pressure alarm events per hour
Num
0
255
3
-
X -
A03 Flow switch bypass time after pump on
s
0
255
50
-
X -
A04 Duration of flow switch input active
s
0
255
10
-
X -
A05 Duration of flow switch input inactive
s
0
255
30
-
X -
A06 Number of flow switch alarm events per hour
Num
0
255
5
-
X -
A07 Bypass compressor thermal switch from
compressor on
s 0
255 0 -
X -
A08 Number of compressor thermal switch alarms/hour Num
0
255
3
-
X -
A09 Number of fan thermal switch alarms/hour
Num
0
255
20
-
X X
A10 Anti-freeze alarm bypass after ON-OFF
Min
0
255
0
-
X X
A11 Anti-freeze alarm activation set point
°C
-127 127
3
-
X X
A12 Hysteresis of anti-freeze alarm
°C
0
25.5
1
-
X -
A13 Anti-freeze alarm events/hour
Num
0
255
3
-
X -
A14 High pressure/temperature activation set point
°C/10-
Kpa*10
0 900 350 -
X
X
A15 High pressure hysteresis
°C/10-
Kpa*10
0 255 30
-
X
X
A16 Low pressure activation bypass
s
0
255
10
-
X
X
A17 Low pressure activation set point
°C/10-
Kpa*10
-500 800 -500
-
X
X
A18 Low pressure hysteresis
°C/10-
Kpa*10
0 255 20
-
X
X
A19 Low pressure alarm events per hour
Num
0
255
3
-
X
X
A20 Machine out of coolant differential
°C
0
255
1
-
X
X
A21 Machine out of coolant bypass
Min
0
255
1
-
X
X
A22 Machine out of coolant duration
Min
0
255
3
-
X
X
A23 Machine out of coolant alarm triggered
Flag
0
1
0
-
X
X
A24 Enable low pressure alarm during defrost
Flag
0
1
0
-
X
X
A25 Input over-temperature set point
°C
0
255
30
-
X
-
A26 Input over-temperature duration
s*10
0
255
60
-
X
-
Settings
Access
Ref.
Pump Parameters
Unit Min Max Factory
General Password
Factory
Adjust.
Hidden
P01 Pump operating mode
0= Continuous operation
1= Pump start upon demand from controller
Flag 0 1
0
-
X X
P02 Delay between pump ON and compressor ON
s
0
255
120
-
X
P03 Delay between compressor OFF and pump OFF
s
0
255
255
-
X
P04 Set start Pump on external temperature
°C/10 -500 800
50
-
X
P05 Set stand-by on external temperature
°C/10 -500 800
0
-
X
P06 Hysteresis Pump on external temperature
°C/10
0
255
10
-
X