Page 16 - IOM BASIC CLIMATIC CONTROLLER
parameters lists
Settings
Access
Ref.
Compressor Parameters
Unit Min Max Factory
General Password
Factory
Adjust.
Hidden
C01 ON-OFF safety time
s*10
0
255
6
-
X
C02 ON-ON safety time
s*10
0
255
30
-
X X
C03 Cooling Control Hysteresis
°C
0
25.5
1
-
X
C04 Heating Control Hysteresis
°C
0
25.5
1.5
-
X
X
C05 Regulation algorithm step intervention delta
°C
0
25.5
1.5
-
X
C06 Compressor – compressor ON interval
s
0
255
60
-
X
C07 Compressor – compressor OFF interval
s
0
255
30
-
X
C08 Capacity step ON interval
s
0
255
60
-
X
Settings
Access
Ref.
Condenser Fan Parameters
Unit Min Max Factory
General Password
Factory
Adjust.
Hidden
F01 Fan output mode
Num 0
2
0
-
X X
F02 Fan pick-up time
s/10
0 255
20
-
X
F03 Fan-Shift
%
0 100
8
-
X X
F04 Impulse Duration triac start
uS*100
0 255 30
-
X X
F05 Functioning in response to compressor request
Flag
0
1
0
-
X X
F06 Minimum speed during cooling
%
0
100
0
-
X -
F07 Maximum silent speed during cooling
%
0
100
100
-
X -
F08 Minimum fan speed temperature/pressure set point
during cooling
°C/10-
Kpa*10
-500 800 120
-
X
F09 Prop. Band during cooling
°C/10-
Kpa*10
0 255 30
-
X
F10 Delta cut-off
°C/10-
Kpa*10
0 255 0
-
X
F11 Cut-off hysteresis.
°C/10-
Kpa*10
0 255 25
-
X
F12 Bypass time cut-off
s
0 255
10
- X
F13 Max speed during cooling
%
0
100
100
-
X
F14 Maximum fan speed temperature/pressure set
point during cooling
°C/10-
Kpa*10
-500 800 150
-
X
F15 Minimum speed during heating
%
0
100
100
-
X
X
F16 Maximum silent speed during heating
%
0
100
100
-
X
X
F17 Minimum fan speed temperature/pressure set point
during heating
°C/10-
Kpa*10
-500 800
10
-
X
X
F18 Prop. Band during heating
°C/10-
Kpa*10
0 255 50
-
X
X
F19 Maximum fan speed during heating
%
0
100
100
-
X
X
F20 Maximum fan speed temperature/pressure set
point during heating
°C/10-
Kpa*10
-500 800 450
-
X
X
F21 Preventilation in cooling mode
s
0
255
0
-
X X
F22 Combined or separate fan control
0= Fans control to separate Circuits
1= Fans control to common Circuits
Flag 0 1
1
-
X X
F23 Fan activation temperature/pressure set point
during defrosting
°C/10-
Kpa*10
-500 800 -500
-
X
X
F24 Fan activation hysteresis during defrosting
°C/10-
Kpa*10
0 255 10
-
X
X
F25 Set 2nd fan step Cooling
°C/10-
Kpa*10
-500 800 175
-
X
F26 Set 3rd fan step Cooling
°C/10-
Kpa*10
-500 800 190
-
X
F27 Set 2nd fan step Heating
°C/10-
Kpa*10
-500 800 -500
-
X
X
F28 Set 3rd fan step Heating
°C/10-
Kpa*10
-500 800 -500
-
X
X
F29 Duty cycle period for "DC" output
s
1
10
5
-
X X