Anti Freeze Parameters
Unit Min Max Factory
General Password
Factory
Adjust.
Hidden
R01 Configuration of electrical heaters in defrost mode
Flag
0
1
1
-
X
X
R02 Configuration of electrical heaters on in cooling
mode
0= Off during cooling
1= On in cooling if called by the Anti freeze program
Flag 0 1
1
-
X X
R03 Configuration of electrical heaters on in heating
mode
0= Off during heating
1= On in heating if called by the Anti freeze program
Flag 0 1
1
-
X
X
R04 Configuration of electrical heater 1 control probe
Num
0
3
1
-
X
X
R05 Configuration of electrical heater 2 control probe
Num
0
3
2
-
X X
R06 Configuration of electrical heaters when Unit is
OFF or on STAND-BY
0= Off
1= On in if called by the Anti freeze program
Flag 0 1
1
-
X X
R07 Set point of electrical heater 1 in heating mode
°C
-7
8
4
-
X
X
R08 Set point of electrical heater 1 in cooling mode
°C
-7
8
4
-
X
R09 Max. set point electrical heaters
°C
-7
127
8
-
X X
R10 Min. set point electrical heaters
°C
-127
8
-7
-
X X
R11 Hysteresis of anti-freeze heaters
°C
0
255
1
-
X X
R12 Parallel electrical heater enable
Flag
0
1
1
-
X
X
R13 Set point of electrical heater 2 in heating mode
°C
-7
8
4
-
X
X
R14 Set point of electrical heater 2 in cooling mode
°C
-7
8
4
-
X
X
R15 Enable supplementary electrical heaters
Flag
0
1
1
-
X
X
R16 Delta of activation of supplementary heater 1
°C
0
25.5
2
-
X
X
R17 Delta of activation of supplementary heater 2
°C
0
25.5
3
-
X
X
R18 Status of with pump OFF
Flag
0
1
0
X
X
Settings
Access
Ref.
Defrost Parameters
Unit Min Max Factory
General Password
Factory
Adjust.
Hidden
D01 Defrost enabled
Flag
0
1
0
-
X
X
D02 Defrost start temperature/pressure
°C/10-
Kpa*10
-500 800
30
-
X
X
D03 Defrost interval
Min
0
255
4
-
X
X
D04 Defrost end temperature/pressure
°C/10-
Kpa*10
-500 800 180
-
X
X
D05 Maximum defrost time
Min
0
255
6
-
X
X
D06 Compressor-reversing valve wait time
s
0
255
5
-
X
X
D07 Drip time
s
0
255
5
-
X
X
D08 Delay between defrosting of circuits
s * 10
0
255
5
-
X
X
D09 Output probe defrost circuit 1
Num
0
3
1
-
X
X
D10 Output probe defrost circuit 2
Num
0
3
1
-
X
X
D11 Delay in compressors on in defrost mode
s
0
255
0
-
X
X
Settings
Access
Ref.
Expansion Card Parameters
Unit Min Max Factory
General Password
Factory
Adjust.
Hidden
N01 Polarity of ID12 ID13 ID14 ID15
Num
0
15
0
-
X
X
N02 Configuration ID12
Num
0
28
0
-
X
X
N03 Configuration ID13
Num
0
28
0
-
X
X
N04 Configuration ID14
Num
0
28
0
-
X
X
N05 Configuration ID15
Num
0
28
0
-
X
X
N06 Configuration relay 9
Num
0
17
0
-
X
X
N07 Configuration relay 10
Num
0
17
0
-
X
X
N08 Configuration relay 11
Num
0
17
0
-
X
X
N09 Configuration relay 12
Num
0
17
0
-
X
X